Mr. Bernard P. Orlan May 8,2002 Indoor Air Quality Assessment Page 3 P. S. 234M ATC Project No. 15-19125-0279

Real-Time Environmental Measurements

ATC collected sixty (60) sets of real-time environmental measurements consisting of fifty one (51) from inside the school building and nine (9) outdoors. All three floors of the school were surveyed. These results are described below.

Field data sheets are found in Attachment 1. Readings began at 2:00 P.M. and concluded after 4:15 P.M.

Temperature

Indoor dry bulb temperature measurements ranged from 69.8 °F to 75.0°F. Twenty-eight (28) indoor measurements for temperature were below the range of 73 to 79°F (at 50 percent relative humidity) as recommended by ASHRAE Standard 55-1992 during the summer season. The outdoor temperature measurements ranged from 64.3 to 70.0 °F.

Relative Humidity

The relative humidity indoors ranged from 47.2 percent to 52.3 percent. All indoor measurements for relative humidity were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 49.0 to 54.1 percent.

CarbonDipxideConcentration

Carbon dioxide concentrations indoors ranged from 437 ppm to 893 ppm. All the measurements were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 421 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1121 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 1 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were also 1 ppm for all readings.

Respirable Particulates (PM2 3)

Respirable particulate concentrations* indoors ranged between 10 pg/m^ to 36 jag/m^ with an average approximately 24 pg/m^ • All measurements collected indoors for respirable particulate concentrations were below the NPAAQS 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter or the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. The outdoor respirable particulate concentration ranged from 33 pg/m^ to 60 pg/m^ with an average of approximately 44 pg/m^.

CITY_21MC100_002920452

NYC-WTC_000397431

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000397431Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →