NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan May 7,2002 Indoor Air Quality Assessment Page 3 P. S. 234M ATC Project No. 15-19125-0279

Real-Time Environmental Measurements

ATC collected sixty (60) sets of real-time environmental measurements consisting of fifty one (51) from inside the school building and nine (9) outdoors. All three floors of the school were surveyed. These results are described below.

Field data sheets are found in Attachment 1. Readings began at 2:00 P.M. and concluded after 16:15 P.M.

Temperature

Indoor dry bulb temperature measurements ranged from 68.3 °F to 75.6°F. Ten (10) indoor measurements for temperature were below the range of 73 to 79°F (at 50 percent relative humidity) as recommended by ASHRAE Standard 55-1992 during the summer season. The outdoor temperature measurements ranged from 58.7 to 61.8 °F.

Relative Humidity

The relative humidity indoors ranged from 40.0 percent to 44.2 percent. All indoor measurements for relative humidity were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 56.0 to 57.0 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 609 ppm to 901 ppm. All the measurements were bellow the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 545 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1245 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

CarbonMpnoxideCpncentration

Carbon monoxide concentrations indoors were 1 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were also 2 ppm for all readings.

Respirable Particulates (PM2,5)

Respirable particulate concentrations* indoors ranged between 19 pg/m^ to 43 pg/m^ with an average 32 pg/m^- All measurements collected indoors for respirable particulate concentrations were below the NPAAQS 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and three (3) measurements were above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. The outdoor respirable particulate concentration ranged from 88 pg/m^ to 96 pg/m^ with an average of 92 pg/m^.

CITY_21MC100^002920441

NYC-WTC_000397421

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000397421Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

IAQ report, PS234M, May 21, 2002

NYC-WTC_000315230

ATC IAQ measurements at PS 234M; BOE program to assess indoor air quality, May 21, 2002.

Similar indexed content

Compare copies and versions →