Indoor air quality report, P.S. 234M, Apr 2002

Machine-extracted title · confidence 44%

Indoor air quality measurements report for P.S. 234M, Apr 2002.

NYC-WTC_000397241–000397244
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan April 9, 2002 Indoor Air Quality Assessment Page 4 P. S. 234M ATC Project No. 15-19125-0279 J

The average PM2.5 concentration for the entire school building was approximately 10 pg/m^. The outdoor respirable particulate concentration ranged from 9 to 25 pg/m^ with an average of 14 pg/m3.

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

TVOC Concentration

TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC concentration was also 0.0 ppm. OBSERVATIONS

During this assessment, ATC noted the following: • The building was occupied at the time of the assessment; • No smoke odor was detected in the building.

FINDINGS

Based on the real-time measurements, the following findings are presented:

1. Concentrations of CO ,CO2and TVOCs were within applicable standards and guidelines. 2. All indoor measurements for temperature were within the range of 68 to 75°F (at 50 percent relative humidity) as recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). 3. Ten (10) indoor measurements for relative humidity were below the ASHRAE- recommended range of 30 to 60 percent for occupant comfort. 4. None of the indoor or outdoor measurements for PM2.5 were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. Also none of the measurements were above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children.

It is our pleasure to provide these indoor air quality services to the New York City Board of Education. If you have any questions about this report, please call (212) 353-8280, extension 211or212.

Sincerely, /I TC ASSOCIA T£S INC. Reviewed by:

Yiannis Efstathiou James R. Cohn, CIH, CSP Senior Project Manager Regional Manager, Industrial Hygiene Division

Attachment

CITY_21MC100_002920220

NYC-WTC_000397244

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000397244Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →