NYC Law Department release
Independent mirror · updated as the City releases more · v1.5.1
☕ Buy me a coffee
← Document results/Unboxed/No folder label
Document / 4 pages

IAQ report, PS 234M, March 2002

Machine-extracted title · confidence 26%

Indoor air quality measurements at PS 234M, prepared for NYC BOE, March 2002.

NYC-WTC_000294458–000294461
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan March 21, 2002 Indoor Air Quality Assessment Page 4 P. S. 234M ATC Project No. 15-19125-0279

The average PM2.5 concentration for the entire school building was approximately 12 pg/m^. The outdoor respirable particulate concentration ranged from 13 to 20 pg/m^ with an average of 16 pg/m3.

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average, TVOC Concentration

TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC concentration was also 0.0 ppm. OBSERVATION During this assessment, ATC noted the following: • The building was occupied at the time of the assessment; • No smoke odor was detected in the building.

FINDINGS

Based on the real-time measurements, the following findings are presented:

1. Concentrations of CO ,CO2and TVOCs were within applicable standards and guidelines, 2. Fifteen (15) indoor measurements for temperature were above the range of 68 to 75°F (at 50 percent relative humidity) as recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). 3. Twelve (12) of the indoor measurements for relative humidity were below the ASHRAE- recommended range of 30 to 60 percent for occupant comfort. 4. None of the indoor or outdoor measurements for PM2,5 were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter or above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals / children.

It is our pleasure to provide these indoor air quality services to the New York City Board of Education. If you have any questions about this report, please call (212) 353-8280, extension 211 or 212,

Sincerely, A TC ASSOCIA TES INC. Reviewed by:

Y j /Yiannis Efsta tu Senior Project Manager James R. Cohn, CIH, CSP Regional Manager, Industrial Hygiene Division

Attachment

CITY_21MC100_003083691

NYC-WTC_000294461

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000294461Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →