IAQ measurements at High School of Economics and Finance, May 13, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗Measurements collected May 10, 2002 for BOE at HSEF.
NYC-WTC_000396502–000396505OCR status: ok · source: pdftotext
NYC 9/11 Public Portal Document
104 East 25th St.. 10th Floor New York. New York 10010 www.atc-enviro.com 212.353.8280 Fax 212.353.8306 ASSOCIATES INC.
May 13, 2002
Mr. Bernard P. Orlan Director, Environmental Health & Safety New York City Board of Education 28-11 Queens Plaza North Long Island City, NY 11101-4008
Re: Indoor Air Quality Assessment High School of Economics and Finance (M833) 100 Trinity Place New York, New York 10006 ATC Project No. 15-19125-0291
Dear Mr. Orlan:
ATC Associates Inc. (ATC) is pleased to provide this report of indoor air quality (lAQ) measurements collected on May 10, 2002 at the referenced school. The New York City Board of Education (BOE) requested these measurements as part of a program to determine if acceptable indoor air quality is being maintained.
SCOPE OF WORK
ATC conducted this evaluation to assess the basic parameters of temperature, relative humidity, carbon dioxide (CO^) and carbon monoxide (CO).
Total volatile organic compounds (TVOCs) and respirable particulates were also measured.
Kevin Fitzpatrick, Environmental Technician of ATC’s New York City office, conducted the assessment. ATC’s findings and conclusions are based on a visual inspection, real-time environmental measurements and conditions present in the school at the time of the assessment.
ATC measured temperature, relative humidity, CO^ and CO with a Q-Trak® Model 8551, manufactured by TSI, Inc.
ATC measured concentrations of respirable particulates (PMj j) with a Dust-Trak® Aerosol Monitor Model 8520, manufactured by TSI, Inc.
ATC measured concentrations of TVOCs using a RAE Systems, Inc. MiniRAE® photoionization detector (PID).
The assessment was performed consistent with generally accepted indoor air quality assessment practices. As with all such assessments, there were inherent limitations created by constraints of time, operational and work practice variability, variations in indoor air quality parameters and sampling and analytical accuracy.
The results of the sampling represent conditions found on the dates of the survey and may not represent conditions found at other times. The information presented in this report should be used
CITY_21MC100_002891412
NYC-WTC_000396502
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000384914
IAQ measurements at High School of Economics and Finance, May 13, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384943
Indoor air quality report for measurements at the school, May 15, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396516
Indoor air quality measurements collected May 13, 2002 for BOE.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259401
ATC indoor air quality measurements collected May 14, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000385035
ATC indoor air quality measurements for BOE at HS of Economics and Finance, May 2002.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000385095
ATC IAQ measurements conducted June 11, 2002 for BOE at the High School of Economics and Finance.
12 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396699
ATC IAQ measurements collected June 11, 2002 at the school for BOE IAQ monitoring.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402542
Indoor air quality measurements collected March 25, 2002 at the referenced school.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384886
IAQ report covering measurements at HS Economics and Finance, 100 Trinity Place.
12 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396474
Indoor air quality measurements collected May 8, 2002 for BOE.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396703
ATC IAQ measurements collected June 12, 2002 for BOE program on acceptable IAQ.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396683
IAQ measurements collected Jun 5, 2002 for school IAQ maintenance check.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000383143
IAQ measurements collected April 23, 2002 at the referenced school.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396575
ATC IAQ measurements collected May 17, 2002 for BOE program on maintaining IAQ.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396531
Measurements collected May 14, 2002; BOE monitoring.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000219394
ATC Associates report on indoor air quality measurements collected at the High School of Economics and Finance on April 24, 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000383107
Indoor air measurements collected April 17, 2002 at the referenced school.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396559
ATC reports IAQ measurements collected May 16, 2002 at the school for BOE review.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Machine-extracted building matches; verify each source. Buildings, never households.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000384914
IAQ measurements at High School of Economics and Finance, May 13, 2002.
Similar indexed content
NYC-WTC_000384943
Indoor air quality report for measurements at the school, May 15, 2002.
Similar indexed content
Indoor air quality measurements collected May 13, 2002 for BOE.
Similar indexed content
ATC indoor air quality measurements collected May 14, 2002.
Similar indexed content
ATC indoor air quality measurements for BOE at HS of Economics and Finance, May 2002.
Similar indexed content