Mr. Bernard P. Orlan . May 1, 2002 Indoor Air Quality Assessment Page 3 H.S. for Leadership & Public Service (M894) ATC Project No. 15-19125-0290 Real-Time Environmental Measurements
ATC collected one hundred and forty (140) sets of real-time environmental measurements consisting of one hundred and twenty-eight (128) in the- school building and twelve (12) outdoors. All fourteen floors of the school were surveyed. Field data sheets are found in the Attachment. Readings were collected in the morning and evening. The results are described below.
Temperature
Indoor dry bulb temperature measurements ranged from 66.5 °F to 77.9 °F. Ninety-eight (98) of the indoor measurements for temperature were below and thirty (30) were within the range of 73 to 79°F (at 50 percent relative humidity),recommended by ASHRAE Standard 55-1992 during the summer season . The outdoor ternperature ranged from 55.6 to 66.0 °F.
Relative Humidity
The relative humidity indoors ranged from 25.1 percent to 36.3 percent. Sixty-three (63) of the indoor measurements for relative humidity were below and sixty-five (65) measurements were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 24.3 to 36.1 percent.
CaHonDioxide Concentration
Carbon dioxide concentrations indoors ranged from 500 ppm to 1171 ppm. All of the indoor measurements for CO2 were below'the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 499 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1199 ppm (background level + 700 ppm). The highest measurement (1171 ppm) was collected in the Gymnasium at 3:10 PM with 0 occupants. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors ranged from 0 ppm to 1 ppm These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged from Ippm to 4ppm.
Respirable Particulates (PM2,s)
Respirable particulate concentrations* indoors ranged between 3 pg/m^ to 69 pg/m^ with an average 9 pg/m^- One of the indoor and eleven (11) of the outdoor measurements for PM2.5 were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter Two (2) of the indoor measurements and all twelve (12) of the outdoor measurements were above the USEPA recommended concentration of 40 pg/m3 for sensitive individuals such as asthmatic people and children. The outdoor respirable particulate concentrations ranged from 52 pg/m3 to 158 pg/m^ with an average of 84 pg/m^.
CITY_21MC100_002918807
NYC-WTC_000394906
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000399222
Indoor air quality measurements at the High School for Leadership & [name]; May 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000296912
IAQ measurements at the referenced school in Apr 2002, part of a program to determine if IAQ is maintained.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000291673
Indoor air quality measurements report for 90 Trinity Place, May 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399520
June 6, 2002 IAQ measurement report for the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000211859
Letter and report from ATC Associates detailing indoor air quality measurements collected at the school on March 25, 2002, to evaluate possible contamination.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000291988
ATC IAQ measurements collected June 11, 2002 for the referenced BOE school.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000291723
Indoor air quality measurements report for HS Leadership & [name], May 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000291960
Report of indoor air quality measurements at 90 Trinity Place, May 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260209
May 2002 IAQ measurements requested by BOE for the school.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399294
Indoor air quality measurements collected May 9, 2002, for the High School for Leadership & [name].
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399402
Indoor air quality measurements collected May 17, 2002, for the High School for Leadership & [name].
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410939
Documentation of accreditation scope for bulk asbestos analysis at ATC lab.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000296912
IAQ measurements at the referenced school in Apr 2002, part of a program to determine if IAQ is maintained.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000291673
Indoor air quality measurements report for 90 Trinity Place, May 2002.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399294
Indoor air quality measurements collected May 9, 2002, for the High School for Leadership & [name].
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000291755
Indoor air quality measurements report for the school at 90 Trinity Place, May 2002.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370557
ATC reports IAQ measurements taken March 26, 2002 at High School for Leadership & [name].
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399508
June 3, 2002 IAQ measurement report for 90 Trinity Place.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
Indoor air quality measurements at the High School for Leadership & [name]; May 2002.
Similar indexed content
NYC-WTC_000296912
IAQ measurements at the referenced school in Apr 2002, part of a program to determine if IAQ is maintained.
Similar indexed content
NYC-WTC_000291673
Indoor air quality measurements report for 90 Trinity Place, May 2002.
Similar indexed content
NYC-WTC_000399520
June 6, 2002 IAQ measurement report for the referenced school.
Similar indexed content
Letter and report from ATC Associates detailing indoor air quality measurements collected at the school on March 25, 2002, to evaluate possible contamination.
Similar indexed content