Indoor air quality report, PS 89M, May 2002

Machine-extracted title · confidence 41%

ATC IAQ report for May 14, 2002 measurements at PS 89M for BOE.

NYC-WTC_000392852–000392855
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan May 15, 2002 Indoor Air Quality Assessment Page 3 P. S. 89M___________ ATC Project No. 15-19125-0297

Reai^Time Enviroyviental Measerements

ATC collected eighty (80) sets of real-time environmental measurements consisting of seventy- one (71) from inside the school building and nine (9) from outdoors. All five floors of the school building were surveyed. These results are described below.

Field data sheets are found in Attachment 1. Readings began at 8:00 A.M. and concluded at approximately 11:30 A.M.

Temperature

Indoor dry bulb temperature measurements ranged from 65.8°F to 72.6 °F. All of the indoor measurements for temperature were below the range of 73 to 79°F (at 50 percent relative humidity) as recommended by the ASHRAF Standard 55-1992 during the summer season . The outdoor temperature measurements ranged from 51.8°F to 53.8 °F.

Relative Humidity

The relative humidity indoors ranged from 33.5 to 44.7 percent. All indoor measurements for relative humidity were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity measurements ranged from 48.5 to 50.0 percent.

Ca^m DioxideConcentratim

Carbon dioxide concentrations indoors ranged from 401 ppm to 1156 ppm. One (1) of the indoor measurement for CO2 was above the ASHRAF Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 400 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1100 ppm (background level + 700 ppm). Carbon dioxide measurements are used as an indicator of available outside makeup air. The primary source of CO2 indoors is occupant respiration. The school building was occupied during ATC’s assessment.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors ranged from 0 ppm to 1 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was 0 ppm for all collected readings.

Respirable Particulates (PM2,5)

Respirable particulate concentrations* indoors ranged between 5 pg/m^ to 24 ug/m^. The average PM2.5 concentration for the entire school building was approximately 11 pg/m^. All of the indoor measurements were below the NPAAQS of 65 pg/m- 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter or the USEPA

CITY_21MC100_002886867

NYC-WTC_000392854

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000392854Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

IAQ report, PS 89M, COE · page 3

NYC-WTC_000313837

ATC indoor air quality measurements conducted June 10, 2002 for PS 89M per BOE request.

Similarity score 0.998 (not a probability)

machine-extracted · confidence unavailable · Check page ↗

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →