Mr. Bernard P. Orlan May 8, 2002 Indoor Air Quality Assessment Page 3 P. S. 89M ATCPrpiectNpJ5-1912520297
Real-Tim^nvironmental Measurements
ATC collected eighty (80) sets of real-time environmental measurements consisting of seventy- one (71) from inside the school building and nine (9) from outdoors. All five floors of the school building were surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began at 8:00 A.M. and concluded at approximately 11 ;30 A.M.
Temperature
Indoor dry bulb temperature measurements ranged from 67.3 °F to 74.8 °F. Forty-nine (49) of the indoor measurements for temperature were below the range of 73 to 79°F (at 50 percent relative humidity) as recommended by the ASHRAE Standard 55-1992 during the summer season . The outdoor temperature measurements ranged from 63.9°F to 65.0 °F.
Relative Humidity
ITie relative humidity indoors ranged from 39.8 to 54.0 percent. All indoor measurements for relative humidity were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity measurements ranged from 55.4 to 57.0 percent.
CarbonDipxideCpncentrqtipn
Carbon dioxide concentrations indoors ranged from 427 ppm to 981 ppm. All indoor measurements for CO2 were within the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 412 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1112 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outside makeup air. The primary soiu-ce of CO2 indoors is occupant respiration. The school building was occupied during ATC’s assessment.
CarbonMpnoxideCpncentrqtion
Carbon monoxide concentrations indoors ranged from 0 ppm to 1 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration were 0 ppm for all collected readings.
Respirable Particulates (PM2,3)
Respirable particulate concentrations* indoors ranged between 11 pg/m^ to 24 pg/m^. The average PM2.5 concentration for the entire school building was approximately 17 pg/m^. All of the indoor measurements were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. The outdoor
CITY_21MC100_002886801
NYC-WTC_000392801
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000369748
ATC IAQ measurements at PS 89M for BOE, May 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000369765
ATC IAQ measurements at PS 89M for BOE, May 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370073
ATC IAQ measurement report for PS 89M at date of June 18, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000392816
ATC report of IAQ measurements at PS 89M, May 9, 2002, for BOE air quality evaluation.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000199006
Cover letter from ATC Associates submitting indoor air quality measurement results for PS89M collected on May 7, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370113
ATC IAQ measurements collected June 24, 2002 at PS 89M.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370077
ATC IAQ measurements conducted June 19, 2002 at PS 89M for BOE.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000369789
ATC IAQ measurements at PS 89M for BOE; May 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370101
ATC IAQ report for PS 89M dated June 21, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370089
ATC IAQ measurements conducted June 20, 2002 at PS 89M for BOE.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000313606
ATC IAQ measurements at the referenced school on May 6, 2002 for BOE.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000369869
INDOOR AIR QUALITY measurements at PS/IS89M for BOE evaluation, dated May 24, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000392816
ATC report of IAQ measurements at PS 89M, May 9, 2002, for BOE air quality evaluation.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370101
ATC IAQ report for PS 89M dated June 21, 2002.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000328353
ATC IAQ measurements collected May 9, 2002 for PS 89M; BOE requested data.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000411165
ATC indoor air quality report for PS 89M; measurements conducted June 13, 2002.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000375541
Report of indoor air quality measurements at PS 150M prior to re-occupancy, March 2002.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000313447
ATC IAQ measurements at P.S. 89M; BOE evaluation, April 11, 2002.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Machine-extracted building matches; verify each source. Buildings, never households.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000369748
ATC IAQ measurements at PS 89M for BOE, May 2002.
Similar indexed content
NYC-WTC_000369765
ATC IAQ measurements at PS 89M for BOE, May 2002.
Similar indexed content
NYC-WTC_000370073
ATC IAQ measurement report for PS 89M at date of June 18, 2002.
Similar indexed content
NYC-WTC_000392816
ATC report of IAQ measurements at PS 89M, May 9, 2002, for BOE air quality evaluation.
Similar indexed content
Cover letter from ATC Associates submitting indoor air quality measurement results for PS89M collected on May 7, 2002.
Similar indexed content