Mr. Bernard P. Orlan June 14, 2002 Indoor Air Quality Assessment Page 3 P. S. 89M ATCProiectNo. 15-19125-0297 Real-Time Environmental Measurements
ATC collected seventy-nine (80) sets of real-time environmental measurements consisting of seventy (70) from inside the school building and ten (10) from outdoors. All five floors of the school building were surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began at 8:00 A.M. and concluded at approximately 10:50 A.M.
Temperature
Indoor dry bulb temperature measurements ranged from 70.0 °F to 75.6 °F. Eleven (11) of the indoor measurements for temperature were below the range of 73 to 79°F (at 50 percent relative humidity) as recommended by the ASHRAE Standard 55-1992 during the summer season. The outdoor temperature measurements ranged from 64.5 °F to 64.6 °F.
Relative Humidity
The relative humidity indoors ranged from 44.1 to 52.4 percent. All of the indoor measurements for relative humidity were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity measurements ranged from 47.1 to 47.6 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 541 ppm to 1161 ppm. All of the indoor measurements for CO2 were within the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 599 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1299 ppm (background level + 700 ppm). Carbon dioxide measurements are used as an indicator of available outside makeup air. The primary source of CO2 indoors is occupant respiration. The school building was occupied during ATC’s assessment.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 1 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were 1 ppm for all collected readings.
Respirable Particulates (PM2,s)
Respirable particulate concentrations* indoors ranged between 8 pg/m^ to 20 ug/mC. The average PM2.5 concentration for the entire school building was approximately 14 pg/mA None of the indoor measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter or above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. The outdoor respirable particulate concentration measurements ranged between 39 pg/m^ to 48 g/m^ with an average of 44 pg/m3.
CONFIDENTIAL, CITY_21MC100_003488587 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008
NYC-WTC_000411167
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000313873
ATC indoor air quality measurements conducted June 13, 2002 for NYC BOE.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000175971
Report detailing indoor air quality measurements conducted at PS 89M to evaluate building air conditions following the WTC collapse.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000369857
Indoor air quality report for PS/89M school, measurements collected May 22, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000369254
IAQ parameters with temperature, humidity, and gas readings.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000369953
ATC IAQ measurements conducted June 4, 2002 at P.S. 89M for BOE air quality evaluation.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000199027
Cover letter from ATC Associates submitting indoor air quality measurement results for PS89M collected on May 22, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370037
IAQ measurements at P.S. 89M collected June 13, 2002 for air quality evaluation.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000313837
ATC indoor air quality measurements conducted June 10, 2002 for PS 89M per BOE request.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000411157
ATC IAQ report for PS 89M; scope includes measurement of basic parameters.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370001
ATC IAQ measurements conducted June 10, 2002 for BOE air quality evaluation.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000313732
IAQ measurements at PS/89M to evaluate school air quality per BOE request.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000369278
IAQ measurements collected June 13, 2002 for school building evaluation.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000370113
ATC IAQ measurements collected June 24, 2002 at PS 89M.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000313976
ATC report of IAQ measurements at P.S. 89M, June 26, 2002, for air quality assessment.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000400137
ATC IAQ report for PS 89M, March 4, 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000394376
Indoor air quality measurements at PS 89M for BOE; April 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370101
ATC IAQ report for PS 89M dated June 21, 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000411230
ATC report of IAQ measurements at PS 89M for NYC BOE evaluation of air quality.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Machine-extracted building matches; verify each source. Buildings, never households.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000313873
ATC indoor air quality measurements conducted June 13, 2002 for NYC BOE.
Similar indexed content
Report detailing indoor air quality measurements conducted at PS 89M to evaluate building air conditions following the WTC collapse.
Similar indexed content
NYC-WTC_000369857
Indoor air quality report for PS/89M school, measurements collected May 22, 2002.
Similar indexed content
NYC-WTC_000369254
IAQ parameters with temperature, humidity, and gas readings.
Similar indexed content
NYC-WTC_000369953
ATC IAQ measurements conducted June 4, 2002 at P.S. 89M for BOE air quality evaluation.
Similar indexed content