Indoor air quality report, PS 89M, 201 Warren St

Machine-extracted title · confidence 58%

IAQ report for April 18, 2002 at PS 89M; BOE requested evaluation.

NYC-WTC_000392649–000392652
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan April 19,2002 Indoor Air Quality Assessment Page 4 P. S. 89M ATC Project No. 15-19125-0297 particulate matter 2.5 micrometers or less in aerodynamic diameter,and USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. The outdoor respirable particulate concentration measurements ranged from 40 to 48 pg m^ with an average of 43 pg/m^. Nine (9) of the outdoor measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children.

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average. TVOC Concentrations TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC concentration was also 0.0 ppm.

OBSERVATIONS During this assessment, ATC noted the following: • The school building was occupied at the time of the assessment. • No smoke odor was detected in the building • The interior of the building appeared clean and free of dust and debris.

FINDINGS Based on the real-time measurements, the following findings are presented:

1. Three (3) of the indoor measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The highest concentrations were detected in Room # 510 (1351ppm with 31 occupants),Room # 432 (1280 ppm with 35 occupants), and Room # 402 (1280 ppm with 31 occupants). The primary source of CO2 indoors is occupant respiration. 2. One (1) of the indoor measurements for temperature were above and sixty nine (69) were within the range of 73 to 79°F (at 50 percent relative humidity) as recommended by the ASHRAE Standard 55-1992 during the summer season . 3. All of the indoor measurements for relative humidity were within the ASHRAE- recommended range of 30 to 60 percent for occupant comfort. 4. Nine (9) of the outdoor measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children.

It is our pleasure to provide these indoor air quality services to the New York City Board of Education. If you have any questions about this report, please call (212) 353-8280, extension 211 or212.

Sincerely, /I TC ASSOCIA TES INC. Reviewed by:

Prasad Doddapaneni James R. Cohn, CIH, CSP Senior Project Manager Regional Manager, Industrial Hygiene Division

Attachment

CITY_21MC100_002886618

NYC-WTC_000392652

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000392652Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →