NYC Law Department release
Independent mirror · updated as the City releases more · v1.5.1
☕ Buy me a coffee
← Document results/Unboxed/No folder label
Document / 4 pages

Indoor air quality report, PS 89M, 201 Warren St

Machine-extracted title · confidence 58%

ATC IAQ measurements report for April 10, 2002 at PS 89M; BOE requested evaluation.

NYC-WTC_000392604–000392607
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan April 11,2002 Indoor Air Quality Assessment Page 3 P. S. 89M AT(’Project No. 15-19125-0297

Real-Time Enmronmemai Measurements

ATC collected eighty (80) sets of real-time environmental measurements consisting of seventy (70) from inside the school building and ten (10) from outdoors. All five floors of the school building were surveyed. These results are described below.

Field data sheets are found in Attachment 1. Readings began at 8:15 A.M. and concluded at approximately 10:00 A.M.

Temperafu/'e

Indoor dry bulb temperature measurements ranged from 70.1 °F to 72.3 °F. All of the indoor measurements were within the range of 68 to 75°F (at 50 percent relative humidity) as recommended by the ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature measurements ranged from 53.9 to 54.3 °F.

Relative Humidity

The relative humidity indoors ranged from 35.4 to 42 percent. All of the indoor measurements were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity measurements ranged from 34.1 to 34.6 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 421 ppm to 1026 ppm. All of the indoor measurements were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 681 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1381 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outside makeup air. The primary source of CO2 indoors is occupant respiration. The school building was occupied during ATC’s assessment.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 1 ppm for all readings.. These concentrations were below the NPAAQS/ASHR.\E guideline of 9 ppm. The outdoor CO concentration was also 1 ppm for all collected readings.

Respirable Particulates (PM2, §)

Respirable particulate concentrations* indoors ranged between 12 pg/m^ to 20 pg/m^. All of the indoor measurements were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The average PM2.5 concentration for the entire school building was approximately 18 pg/m^. The PM2.5 average concentrations (indoor and outdoor) were below the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. The outdoor respirable particulate concentration measurements ranged from 30 to 33 pg/m^ with an average of 32 pg/mT

CITY_21MC100_002886537

NYC-WTC_000392606

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000392606Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →