Indoor air quality report, High School of Economics, Jun 2002

Machine-extracted title · confidence 42%

ATC IAQ measurements collected June 12, 2002 for BOE at the High School of Economics and Finance.

NYC-WTC_000385099–000385102
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr, Bernard P. Orlan June 13,2002 Indoor Air Quality Assessment Page 3 H.S. of Economics and Finance (M8331________ ATC Project No. 15-19125-0291 Real-Time Environmental Measurements

ATC collected one hundred and six (106) sets of real-time environmenul measurements consisting of ninety-four (94) inside the school building and twelve (12) outdoors. Field data sheets are found in the Attachment. Readings were collected between morning to evening. The results are described below.

Temperature

Indoor dry bulb temperature measurements ranged from 76.4 to 85.4 °F. Ninety-one (91) of the indoor measurements for temperature were above and none of the measurements were below the range of 73 °F to 79®F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the summer season. The outdoor temperature measurements ranged from 80.9 “F to 89.3 °F.

Relative Humiditv

The relative humidity indoors ranged from 40.0 percent to 62.6 percent. Three (3) the indoor measurements for relative humidity were above and none of the measurements were below the ASHRAE recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 56.5 to 67.6 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 470 ppm to 1452 ppm. Eight (8) of the indoor measurements for COj were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) COj concentration was 558 ppm. Therefore, the maximum acceptable level of CO, at this location was 1258 ppm (background level + 700 ppm). The highest concentration (1452 ppm) was recorded in room 604 around 2:26 PM with 21 occupants. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as aa indicator of available outdoor air. The primary source of COj indoors is occupant respiration.

Carbon ATonoxtde Concentration

Carbon monoxide concentrations indoors ranged from 1 ppm to 2 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged from 1 ppm to 4 ppm.

Respirable Particulates

Respirable particulate concentrations* indoors ranged between 9 pg/m’ to 152 pg/m’ with an average of 33 pg/m’- Ten (10) of ths indoor measurements for respirable particulates were above the NPAAQS of 65 pg/m’ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and thirteen (13) of the indoor measurements were above the USEPA recommended concentration of 40 pg/m’ for sensitive individuals and children. The respirable concentrations outdoors ranged between 134 pg/m’ to 194 pg/m’ with an average of 164 pg/m’ ■

CITY_21MC100_002882517

NYC-WTC_000385101

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000385101Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000396474

Indoor air quality measurements collected May 8, 2002 for BOE.

Similar indexed content

NYC-WTC_000396683

IAQ measurements collected Jun 5, 2002 for school IAQ maintenance check.

Similar indexed content

NYC-WTC_000396703

ATC IAQ measurements collected June 12, 2002 for BOE program on acceptable IAQ.

Similar indexed content

NYC-WTC_000385035

ATC indoor air quality measurements for BOE at HS of Economics and Finance, May 2002.

Similar indexed content

Compare copies and versions →