Mr, Bernard P. Orlan June 13,2002 Indoor Air Quality Assessment Page 3 H.S. of Economics and Finance (M8331________ ATC Project No. 15-19125-0291 Real-Time Environmental Measurements
ATC collected one hundred and six (106) sets of real-time environmenul measurements consisting of ninety-four (94) inside the school building and twelve (12) outdoors. Field data sheets are found in the Attachment. Readings were collected between morning to evening. The results are described below.
Temperature
Indoor dry bulb temperature measurements ranged from 76.4 to 85.4 °F. Ninety-one (91) of the indoor measurements for temperature were above and none of the measurements were below the range of 73 °F to 79®F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the summer season. The outdoor temperature measurements ranged from 80.9 “F to 89.3 °F.
Relative Humiditv
The relative humidity indoors ranged from 40.0 percent to 62.6 percent. Three (3) the indoor measurements for relative humidity were above and none of the measurements were below the ASHRAE recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 56.5 to 67.6 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 470 ppm to 1452 ppm. Eight (8) of the indoor measurements for COj were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) COj concentration was 558 ppm. Therefore, the maximum acceptable level of CO, at this location was 1258 ppm (background level + 700 ppm). The highest concentration (1452 ppm) was recorded in room 604 around 2:26 PM with 21 occupants. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as aa indicator of available outdoor air. The primary source of COj indoors is occupant respiration.
Carbon ATonoxtde Concentration
Carbon monoxide concentrations indoors ranged from 1 ppm to 2 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged from 1 ppm to 4 ppm.
Respirable Particulates
Respirable particulate concentrations* indoors ranged between 9 pg/m’ to 152 pg/m’ with an average of 33 pg/m’- Ten (10) of ths indoor measurements for respirable particulates were above the NPAAQS of 65 pg/m’ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and thirteen (13) of the indoor measurements were above the USEPA recommended concentration of 40 pg/m’ for sensitive individuals and children. The respirable concentrations outdoors ranged between 134 pg/m’ to 194 pg/m’ with an average of 164 pg/m’ ■
CITY_21MC100_002882517
NYC-WTC_000385101
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000396474
Indoor air quality measurements collected May 8, 2002 for BOE.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396683
IAQ measurements collected Jun 5, 2002 for school IAQ maintenance check.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396703
ATC IAQ measurements collected June 12, 2002 for BOE program on acceptable IAQ.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384943
Indoor air quality report for measurements at the school, May 15, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000385035
ATC indoor air quality measurements for BOE at HS of Economics and Finance, May 2002.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384246
Indoor air quality measurements collected on March 22, 2002 at HS Economics & Finance.
12 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396699
ATC IAQ measurements collected June 11, 2002 at the school for BOE IAQ monitoring.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396620
IAQ measurements collected May 22, 2002 for BOE IAQ maintenance program.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396516
Indoor air quality measurements collected May 13, 2002 for BOE.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259401
ATC indoor air quality measurements collected May 14, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384250
Chain-of-custody for potable water sampling at Trinity Place site, March 2002.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259511
ATC IAQ measurements report for June 12, 2002 at the school.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000396667
IAQ measurements collected May 30, 2002 for BOE IAQ program.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396620
IAQ measurements collected May 22, 2002 for BOE IAQ maintenance program.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259515
ATC IAQ measurements report for June 13, 2002 at the school.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000219896
Cover letter and summary report detailing indoor air quality measurements conducted at the High School of Economics and Finance.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396645
ATC IAQ measurements collected May 24, 2002 for IAQ assessment.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000180045
Letter from ATC Associates reporting indoor air quality measurements collected at a school on May 15, 2002.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Machine-extracted building matches; verify each source. Buildings, never households.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
Indoor air quality measurements collected May 8, 2002 for BOE.
Similar indexed content
IAQ measurements collected Jun 5, 2002 for school IAQ maintenance check.
Similar indexed content
ATC IAQ measurements collected June 12, 2002 for BOE program on acceptable IAQ.
Similar indexed content
NYC-WTC_000384943
Indoor air quality report for measurements at the school, May 15, 2002.
Similar indexed content
ATC indoor air quality measurements for BOE at HS of Economics and Finance, May 2002.
Similar indexed content