Mt. Bernard P. Orlan June 11,2002 Indoor Air Quality Assessment Page 3 H.S. of Economics and Finance (M833)________ ATC Proiect No. 15-19125-0291 Real-Time Environmental Measurements
ATC collected one hundred and six (106) sets of real-time environmenral measurements consisting of ninety-four (94) inside the school building and twelve (12) outdoors. Field data sheets are found in the Attachment. Readings were collected between morning to evening. The results are described below.
Temperature
Indoor dry bulb temperature measurements ranged from 75.2 °F to 82.4 °F. Seventy-four (74) of the indoor measurements for temperature were above and none of the measurements were below the range of 73 °F to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the summer season. The outdoor temperature measurements ranged from 76.2 °F to 87.2 °F.
Relative Humidity
The relative humidity indoors ranged from 33.9 percent to 47.5 percent. All the indoor measurements for relative humidity were within the ASHRAE recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 31,5 to 45.5 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 501 ppm to 1711 ppm. Eleven (11) of the indoor measurements for CO2 were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 574 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1274 ppm (background level + 700 ppm). The highest concentration (1711 ppm) was recorded on the 3rd floor staircase 3:29 PM with 17 occupants. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO? indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors ranged from 1 ppm to 2 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged from 1 ppm to 3 ppm.
Respirable Particulates (PMo^)
Respirable particulate concentrations* indoors ranged between 3 pg/m^ to 66 pg^rn^ with an average of 14 gg/m^- One (1) of the indoor measurements for respirable particulates was above the NPAAQS of 65 pgy'm^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and six (6) of the indoor measurements was above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. The respirable concentrations outdoors ranged between 33 pg/m^ to 74 pg/m^ with an average of 51 pg/m3 ■
CITY_21MC100_002882483
NYC-WTC_000385093
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000396695
ATC IAQ measurements conducted June 10, 2002 for BOE program to maintain acceptable IAQ.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396691
ATC IAQ measurements from June 7, 2002 at the referenced school for BOE monitoring.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259503
ATC IAQ measurements report for June 7, 2002 at the school.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000385087
ATC IAQ measurements collected June 7, 2002 at the school.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396687
ATC reports IAQ measurements at High School of Economics and Finance, June 2002, per BOE request.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000385095
ATC IAQ measurements conducted June 11, 2002 for BOE at the High School of Economics and Finance.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384943
Indoor air quality report for measurements at the school, May 15, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396488
Indoor air quality measurements collected May 9, 2002 for BOE.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000404562
IAQ measurements collected on Apr 26, 2002; BOE program.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384900
May 9-10 IAQ measurements at the school, part of BOE program.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259401
ATC indoor air quality measurements collected May 14, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384111
IAQ report for High School of Economics and Finance, March 2002, coordinated by ATC.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000396695
ATC IAQ measurements conducted June 10, 2002 for BOE program to maintain acceptable IAQ.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000383193
IAQ measurements collected April 29, 2002 for BOE at the referenced school.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384111
IAQ report for High School of Economics and Finance, March 2002, coordinated by ATC.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396687
ATC reports IAQ measurements at High School of Economics and Finance, June 2002, per BOE request.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396699
ATC IAQ measurements collected June 11, 2002 at the school for BOE IAQ monitoring.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000219896
Cover letter and summary report detailing indoor air quality measurements conducted at the High School of Economics and Finance.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Machine-extracted building matches; verify each source. Buildings, never households.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
ATC IAQ measurements conducted June 10, 2002 for BOE program to maintain acceptable IAQ.
Similar indexed content
ATC IAQ measurements from June 7, 2002 at the referenced school for BOE monitoring.
Similar indexed content
ATC IAQ measurements report for June 7, 2002 at the school.
Similar indexed content
NYC-WTC_000385087
ATC IAQ measurements collected June 7, 2002 at the school.
Similar indexed content
ATC reports IAQ measurements at High School of Economics and Finance, June 2002, per BOE request.
Similar indexed content