Mr. Bernard P. Orlan May 29. 2002 Indoor Air Quality Assessment Page 4 H.S. of Economics and Finance (M833) ATC Proiect No. 15-19125-0291

T70C Concentration

TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC concentration was also 0.0 ppm.

OBSERVATIONS

During this assessment, ATC noted the following: • The interior of the building appeared clean and free of dust and debris: • The building was occupied at the time of the assessment; • No smoke odor was detected in the building;

FINDINGS

Based on the real-time measurements, the following findings are presented:

1. Indoor concentrations of CO2, CO and TVOCs were below applicable standards and guidelines. 2. Sixty-seven (67) of the indoor measurements for temperature were above and none of the measurements were below the range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the summer season. 3. All of the indoor measurements for relative humidity were within the ASHRAE recommended range of 30 to 60 percent for occupant comfort. 4. None of the indoor measurements for respirable particulates were above the NPAAQS of 65 pg/m3 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter or above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children.

It is our pleasure to provide these indoor air quality services to the New York City Board of Education. If you have any questions about this report, please call (212) 353-8280, extension 211 or 212.

Sincerely, A TC ASSOCrA TES INC. Reviewed by: I

James R. Cohn, CIH, CSP Senior Pt^ct Manager Regional Manager, Industrial Hygiene

Attachment

CITY_21MC100_002882334

NYC-WTC_000385066

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000385066Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000396659

IAQ report for measurements collected May 28, 2002 under BOE program.

Similar indexed content

NYC-WTC_000396715

ATC IAQ measurements collected June 17, 2002 as part of BOE monitoring.

Similar indexed content

NYC-WTC_000385111

ATC IAQ measurements collected June 17, 2002 for BOE at the High School of Economics and Finance.

Similar indexed content

NYC-WTC_000404467

IAQ measurements at 100 Trinity Place, performed April 9, 2002.

Similar indexed content

Compare copies and versions →