Mr. Bernard P. Orlan May 29,2002 Indoor Air Quality Assessment Page 3 H.S. of Economics and Finance (M833)________ ATC Project No. 15-19125-0291 Real-Time Environmental Measurements
ATC collected one hundred (100) sets of real-time environmental measurements consisting of eighty-eight (88) inside the school building and twelve (12) outdoors. Field data sheets are found in the Attachment. Readings were collected between morning to evening. The results are described below.
Temperature
Indoor dry bulb temperature measurements ranged from 77.2 °F to 82.1 °F. Sixty-seven (67) of the indoor measurements for temperature were above and none of the measurements were below the range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAF Standard 55-1992 during the summer season. The outdoor temperature measurements ranged from 75.4 °F to 82.3 °F.
Relative Humidity
The relative humidity indoors ranged from 42.1 percent to 54.1 percent. All of the indoor measurements for relative humidity were within the ASHRAF recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 54.9 to 62.2 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 512 ppm to 1184 ppm. All of the indoor measurements for CO2 were below the ASHRAF Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 592 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1292 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors ranged from Ippm to 2 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged from 1 ppm to 3 ppm.
Respirable Particulates (PM2,5)
Respirable particulate concentrations* indoors ranged between 4 pg/m^ to 26 pg/m^ with an average of 11 pg/m^- None of the indoor measurements for respirable particulates were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter or above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. The respirable concentrations outdoors ranged between 43 pg/m^ to 89 pg/m^ with an average of 67 pg/m^ ■
* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.
CITY_21MC1OO_OO2882333
NYC-WTC_000385065
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000396659
IAQ report for measurements collected May 28, 2002 under BOE program.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396715
ATC IAQ measurements collected June 17, 2002 as part of BOE monitoring.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000404522
IAQ measurements collected at the referenced school; BOE program (Apr 22, 2002).
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000385111
ATC IAQ measurements collected June 17, 2002 for BOE at the High School of Economics and Finance.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000404467
IAQ measurements at 100 Trinity Place, performed April 9, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396719
ATC IAQ measurements collected June 18, 2002 for BOE IAQ maintenance.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000385119
ATC IAQ measurements collected June 19, 2002 for BOE at the High School of Economics and Finance.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000385049
ATC May–June 2002 IAQ report correspondence with BOE about school's air quality.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259471
ATC indoor air quality report for the BOE-ordered measurements at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396575
ATC IAQ measurements collected May 17, 2002 for BOE program on maintaining IAQ.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259208
Report of indoor air quality measurements collected April 22, 2002 for BOE.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396645
ATC IAQ measurements collected May 24, 2002 for IAQ assessment.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000219896
Cover letter and summary report detailing indoor air quality measurements conducted at the High School of Economics and Finance.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396659
IAQ report for measurements collected May 28, 2002 under BOE program.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396723
ATC IAQ measurements collected June 19, 2002 under BOE IAQ program.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396645
ATC IAQ measurements collected May 24, 2002 for IAQ assessment.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396715
ATC IAQ measurements collected June 17, 2002 as part of BOE monitoring.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259531
ATC IAQ measurements report for June 20, 2002 at the school.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Machine-extracted building matches; verify each source. Buildings, never households.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
IAQ report for measurements collected May 28, 2002 under BOE program.
Similar indexed content
ATC IAQ measurements collected June 17, 2002 as part of BOE monitoring.
Similar indexed content
NYC-WTC_000404522
IAQ measurements collected at the referenced school; BOE program (Apr 22, 2002).
Similar indexed content
ATC IAQ measurements collected June 17, 2002 for BOE at the High School of Economics and Finance.
Similar indexed content
IAQ measurements at 100 Trinity Place, performed April 9, 2002.
Similar indexed content