ATC IAQ field data for High School of Economics and Finance (M833) project 15-19125-0291.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗ATC May–June 2002 IAQ report correspondence with BOE about school's air quality.
NYC-WTC_000385049–000385052OCR status: ok · source: pdftotext
NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan May 28, 2002 Indoor Air Quality Assessment Page 3 H.S. of Economics and Finance (M833) ATC Protect No. 15-19125-0291 Real-Time Environmental Measure.ments
ATC collected one hundred (100) sets of real-time environmental measurements consisting of eighty-eight (88) inside the school building and twelve (12) outdoors. Field data sheets are found in the Attachment. Readings were collected between morning to evening. The results are described below.
Temperature
Indoor dry bulb temperature measurements ranged from 72.1 °F to 79.3 °F. Two (2) of the indoor measurements for temperature were below and three (3) indoor temperature measurements were above the range of 73 to 79*F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the summer season. The outdoor temperature measurements ranged from 69.9 °F to 84.5 °F.
Relative Humidity
The relative humidity indoors ranged from 36.1 percent to 45.7 percent. All of the indoor measurements for relative humidity were within the ASHRAE recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 40.4 to 47.1 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 499 ppm to 1223 ppm. All of the indoor measurements for CO2 were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 561 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1261 ppm (background level -1- 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors ranged was 1 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations was 1 ppm for all collected readings.
Respirable Particulates (PM}. 5)
Respirable particulate concentrations* indoors ranged between 6 pg/m^ to 19 pg/m^ with an average of 12 pg/m^- None of the indoor measurements for respirable particulates were above the NPzVAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter or above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. The respirable concentrations outdoors ranged between 29 pg/m^ to 41 pg/m3 with an average of 34 pg/m^ ■
* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.
CITY_21MC100_002882318
NYC-WTC_000385051
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000404508
ATC IAQ field data for High School of Economics and Finance (M833) project 15-19125-0291.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396715
ATC IAQ measurements collected June 17, 2002 as part of BOE monitoring.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396659
IAQ report for measurements collected May 28, 2002 under BOE program.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000404504
IAQ measurements at the referenced school; BOE program participation (Apr 17, 2002).
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396645
ATC IAQ measurements collected May 24, 2002 for IAQ assessment.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000385115
ATC IAQ measurements collected June 18, 2002 for BOE at the High School of Economics and Finance.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396719
ATC IAQ measurements collected June 18, 2002 for BOE IAQ maintenance.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396723
ATC IAQ measurements collected June 19, 2002 under BOE IAQ program.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384959
Indoor air quality measurements collected May 15-16, 2002 for the school.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000385111
ATC IAQ measurements collected June 17, 2002 for BOE at the High School of Economics and Finance.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000404522
IAQ measurements collected at the referenced school; BOE program (Apr 22, 2002).
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396727
ATC IAQ measurements collected June 20, 2002 for BOE IAQ monitoring.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000259196
ATC indoor air quality measurements conducted April 17, 2002 for BOE review.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000383165
ATC notes IAQ measurements performed April 25, 2002 for BOE.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384959
Indoor air quality measurements collected May 15-16, 2002 for the school.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384928
IAQ measurements collected May 14, 2002 for school project.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259244
ATC report of IAQ measurements collected April 25, 2002 for BOE.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396516
Indoor air quality measurements collected May 13, 2002 for BOE.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Machine-extracted building matches; verify each source. Buildings, never households.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000404508
ATC IAQ field data for High School of Economics and Finance (M833) project 15-19125-0291.
Similar indexed content
ATC IAQ measurements collected June 17, 2002 as part of BOE monitoring.
Similar indexed content
IAQ report for measurements collected May 28, 2002 under BOE program.
Similar indexed content
NYC-WTC_000404504
IAQ measurements at the referenced school; BOE program participation (Apr 17, 2002).
Similar indexed content
ATC IAQ measurements collected May 24, 2002 for IAQ assessment.
Similar indexed content