IAQ report, HS Economics & Finance, 2002

Machine-extracted title · confidence 25%

IAQ measurements collected at HS Economics & Finance per BOE request; March 2002.

NYC-WTC_000384241–000384245
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan March 22,2002 Indoor Air Quality Assessment Page 3 H.S. of Economics and Finance fM833)________ AICProiectNo^l5;19125-0291 Real-Time Environmental measurements

ATC collected one hundred (100) sets of real-time environmental measurements consisting of eighty-eight (88) in the school building and twelve (12) outdoors. Field data sheets are found in the Attachment. Readings began at 8:03 A.M. and concluded after 2:51 P.M. The results are described below.

Temperature

Indoor dry bulb temperature measurements ranged from 64.8 °F to 75 °F. Fourteen (14) of the indoor measurements for temperature were below and seventy-four (74) were within the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature ranged from 46.5 to 63.1 °F.

Relative Humidity

The relative humidity indoors ranged from 26.7 percent to 41.9 percent. Forty-eight (48) of the indoor measurements for relative humidity are below and forty (40) were within the ASHRAE recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 26.1 to 33.4 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 339 ppm to 1442 ppm. Three (3) of the indoor measurements for CO2 were above the ASHRAE Standard 62*1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 465 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1165 ppm (background level + 700 ppm). The highest reading (1442 ppm) was measured in the cafeteria at approximately at 1:29 PM with 160 occupants. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were between 1 to 3 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration ranged from 2 to 5 ppm.

Respirable Particulates (PM2,3)

Respirable particulate concentrations* indoors ranged between 4 pg/m^ to 53 pg/m^ with an average 12 pg/m^- All of the indoor measurements were below the NPAAQS of 65 pg/m^ 24- hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. One (1) of the eighty-eight (88) instantaneous indoor readings was above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. The outdoor respirable particulate concentration ranged from 37 pg/m^ to 74 pg/m^ with an average of 64 pg/m3. Seven (7) of the outdoor measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter.

CITY_21MC100_013428794

NYC-WTC_000384243

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000384243Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000219378

ATC Associates report on indoor air quality measurements collected at the High School of Economics and Finance on April 8, 2002.

Similar indexed content

NYC-WTC_000404462

IAQ measurements at HS of Economics and Finance, April 8, 2002.

Similar indexed content

NYC-WTC_000402524

Indoor air quality measurements collected March 19, 2002 at the referenced school.

Similar indexed content

Compare copies and versions →