Mr. Bernard P. Orlan January 30. 2002 Indoor Air Quality Assessment Page 3 P. S. 89M ATC Project No. 15-19125-0297

Real-Time Environmental Measurements

ATC collected eighty-six (86) sets of real-time environmental measurements consisting of six (6) outdoors in the morning (A.M.) followed by sixty-four (64) inside and sixteen (16) outside in the afternoon (P.M.). All five floors of the school were surveyed. These results are described below.

Field data sheets are found in Attachment 1. Readings began at 8:00 A.M. and concluded after 4:00 P.M.

Temoerature

Indoor dry bulb temperature measurements ranged from 69.5°F to 73.6°F (P.M.). Only four measurements were below the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). These were A.M. readings on the 1st floor. The outdoor temperature measurements averaged 52.8 °F to 59.0 °F (A.M.) and from 66.1°F to 75.3 °F (P.M.).

Relative Humidity

The relative humidity indoors ranged from 28.9 to 38.4 percent (P.M.). Fifty-seven (57) P.M. readings measurements were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The remainder was below the recommended range. The outdoor relative humidity averaged 53.2 percent (A.M.) and 67.0 percent (P.M.).

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 519 to 840 ppm (P.M.). None of the CO2 measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentrations averaged 419.3 ppm (A.M.) and 491.9 ppm (P.M.). Therefore, the maximum acceptable level of CO2 at this location was 1119.3 ppm (background level + 700 ppm). Lex els above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration. The 4^ and 5^ floors of the school building were occupied during ATC’s assessment.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 0-1 ppm for all readings. These concentrations were below the ASHRAE guideline of 9 ppm. The outdoor CO concentration was also 0-2 ppm.

Respirable Particulates (PM2,j)

Respirable particulate concentrations* indoors ranged from 25 pg/m^ to 49 pg/m^ (P.M.). All indoor measurements were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The average PM2,5

CITY_21MC100_003775366 NYC-WTC_000384066

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000384066Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →