IAQ report, PS89M, Mar 2002

Machine-extracted title · confidence 50%

Indoor air quality measurements collected March 7, 2002 at PS89M for BOE evaluation.

NYC-WTC_000383791–000383795
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan March 8, 2002 Indoor Air Quality Assessment Page 3 P. S. 89M_______________________________ ATC Proiect No. 15-19125-0297 Real-Time Environmental Measurements

ATC collected eighty (80) sets of real-time environmental measurements consisting of seventy-e (70) from inside the school building and ten (10) from outdoors. All five floors of the school building were surveyed. These results are described below.

Field data sheets are found in Attachment 1. Readings began at 8:15 A.M. and concluded at approximately 11:30 A.M.

Temperature

Indoor dry bulb temperature measurements ranged from 71.8 °F to 76 °F. Seventeen (17) measurements were above and fifty-three (53) measurements are within the range of 68 °F to 75 °F (at 50 percent relative humidity) as recommended by the ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature measurements ranged from 48.2 to 52.3 °F.

Relative Humidity

The relative humidity indoors ranged from 19.6 to 26.1 percent. All of the measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity measurements ranged from 24.4 to 42.4 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 576 ppm to 1232 ppm. Two (2) of the CO2 measurements were above and seventy-eight (78) were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 564 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1164 ppm (background level + 700 ppm). The highest CO2 measurement was collected from room 402 at 10:30 AM with 37 occupants. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outside makeup air. The primary source of CO2 indoors is occupant respiration. The school building was occupied during ATC’s assessment.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 0 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was also 0 ppm for all collected readings.

Respirable Particulates (PM2,5)

Respirable particulate concentrations indoors ranged between 24 pg/m^ to 55 pg m-\ None of the measurements were above the NPAAQS of 65 ug m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The average PM2.5 concentration for the entire school building was approximately 38 pg/mA Sixteen (16) of the seventy (70) instantaneous indoor measurements were above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children. The

CITY_21MC100_002880868

NYC-WTC_000383793

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000383793Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

IAQ report for PS 89M, Apr 2002 · Box unavailable

NYC-WTC_000220651

Formal indoor air quality assessment report submitted to the Board of Education regarding measurements taken at PS 89M on April 17, 2002.

14 shared non-person entities · 1 shared topics · similarity 0.998

machine-extracted · confidence unavailable · Check page ↗

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000199010

Cover letter from ATC Associates submitting indoor air quality measurement results for PS89M collected on May 8, 2002.

Similar indexed content

Compare copies and versions →