Indoor air quality report, PS 89M

Machine-extracted title · confidence 59%

IAQ measurements report for PS 89M, March 8, 2002, ATC.

NYC-WTC_000400178–000400181
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan March 11, 2002 Indoor Air Quality Assessment Page 3 P. S. 89M ____________________________ ATC Project No. 15-19125-0297 Real-Time environmental Measurements

ATC collected eighty (80) sets of real-time environmental measurements consisting of seventy-e (70) from inside the school building and ten (10) from outdoors. All five floors of the school building were surveyed. These results are described below.

Field data sheets are found in Attachment 1. Readings began at 8:05 A.M. and concluded at approximately 11:30 A.M.

Temperature

Indoor dry bulb temperature measurements ranged from 70.9 °F to 75.7°F. Two (2) measurements were above and sixty -eight (68) measurements are within the range of 68 °F to 75 °F (at 50 percent relative humidity) as recommended by the ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature measurements ranged from 51 to 70.3 °F.

Relative Humidity

The relative humidity indoors ranged from 26.5 to 32.3 percent. Sixty-four of the measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity measurements ranged from 33.4 to 70.3 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 619 ppm to 1217 ppm. All the CO2 measurements were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 572 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1272 ppm (background level + 700 ppm). The highest CO2 measurement was collected from room 510 at 9:30 AM with 26 occupants. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outside makeup air. The primary source of CO2 indoors is occupant respiration. The school building was occupied during ATC’s assessment.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors ranges from 0-1 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was also 1 ppm for all collected readings.

Respirable Particulates (PM2 3)

Respirable particulate concentrations indoors ranged between 40 pg/m^ to 76 pg/m^. Twenty- one(21) of the measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The average PM?.3 concentration for the entire school building was approximately 63 pg/m^.Sixty- nine (69) of the seventy (70) instantaneous indoor measurements were above the USEPA recommended concentration of 40 pg/m3 for sensitive individuals such as asthmatic people and

CITY_21MC100_002923260

NYC-WTC_000400180

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000400180Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Page similarity is temporarily unavailable or this page has no indexed vector.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

IAQ report, PS89M, Mar 2002

NYC-WTC_000383804

Indoor air quality measurements collected March 8, 2002 at PS89M for BOE evaluation.

Similar indexed content

Compare copies and versions →