NYC 9/11 Public Portal Document
CYATC 104 East 25th St.. 10th Floor New York. New York 10010 www.atc-enviro.com 212.353.8280 Fax 212.353.8306 ASSOCIATES INC.
April 26, 2002
Mr. Bernard P. Orlan Director, Environmental Health & Safety New York City Board of Education 28-11 Queens Plaza North Long Island City, NY 11101 -4008
Re: Indoor Air Quality Assessment High School of Economics and Finance (M833) 100 Trinity Place New York, New York 10006 ATC Project No. 15-19125-0291
Dear Mr. Orlan:
ATC Associates Inc. (ATC) is pleased to provide this report of indoor air quality (lAQ) measurements collected on April 25, 2002 at the referenced school. The New York City Board of Education (BOE) requested these measurements as part of a program to determine if acceptable indoor air quality is being maintained.
SCOPE OF WORK
ATC conducted this evaluation to assess the basic parameters of temperature, relative humidity, carbon dioxide (CO2) and carbon monoxide (CO).
Total volatile organic compounds (TVOCs) and respirable particulates were also measured.
Deycer Giraldo, environmental technician of ATC’s New York City office, conducted the assessment. ATC’s findings and conclusions are based on a visual inspection, real-time environmental measurements and conditions present in the school at the time of the assessment.
ATC measured temperature, relative humidity, CO2 and CO with a Q-Trak® Model 8551, manufactured by TSI, Inc.
ATC measured concentrations of respirable particulates (PM2.5) with a Dust-Trak® Aerosol Monitor Model 8520, manufactured by TSI, Inc.
ATC measured concentrations of TVOCs using a RAE Systems, Inc. MiniRAE® photoionization detector (PID).
The assessment was performed consistent with generally accepted indoor air quality assessment practices. As with all such assessments, there were inherent limitations created by constraints of time, operational and work practice variability, variations in indoor air quality parameters and sampling and analytical accuracy.
CITY_21MC100_002879949
NYC-WTC_000383165
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000383107
Indoor air measurements collected April 17, 2002 at the referenced school.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000404504
IAQ measurements at the referenced school; BOE program participation (Apr 17, 2002).
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396723
ATC IAQ measurements collected June 19, 2002 under BOE IAQ program.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000404508
ATC IAQ field data for High School of Economics and Finance (M833) project 15-19125-0291.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000404489
IAQ measurements conducted at the referenced school as part of BOE program (Apr 16, 2002).
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396645
ATC IAQ measurements collected May 24, 2002 for IAQ assessment.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000223592
Report of indoor air quality measurements collected at the High School of Economics and Finance on June 24, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396711
ATC IAQ measurements collected June 14, 2002 for BOE IAQ program.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000383129
IAQ measurements conducted April 22, 2002 for BOE at the school.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396671
IAQ field measurements collected Jun 3, 2002 for IAQ monitoring.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000385115
ATC IAQ measurements collected June 18, 2002 for BOE at the High School of Economics and Finance.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259523
ATC IAQ measurements report for June 18, 2002 at the school.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000383088
IAQ measurements at High School of Economics and Finance conducted April 15, 2002.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396691
ATC IAQ measurements from June 7, 2002 at the referenced school for BOE monitoring.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396695
ATC IAQ measurements conducted June 10, 2002 for BOE program to maintain acceptable IAQ.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000219394
ATC Associates report on indoor air quality measurements collected at the High School of Economics and Finance on April 24, 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396687
ATC reports IAQ measurements at High School of Economics and Finance, June 2002, per BOE request.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000223592
Report of indoor air quality measurements collected at the High School of Economics and Finance on June 24, 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Machine-extracted building matches; verify each source. Buildings, never households.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000383107
Indoor air measurements collected April 17, 2002 at the referenced school.
Similar indexed content
NYC-WTC_000404504
IAQ measurements at the referenced school; BOE program participation (Apr 17, 2002).
Similar indexed content
ATC IAQ measurements collected June 19, 2002 under BOE IAQ program.
Similar indexed content
NYC-WTC_000404508
ATC IAQ field data for High School of Economics and Finance (M833) project 15-19125-0291.
Similar indexed content
NYC-WTC_000404489
IAQ measurements conducted at the referenced school as part of BOE program (Apr 16, 2002).
Similar indexed content