NYC-WTC_000383111–000383114OCR status: ok · source: pdftotext
NYC 9/11 Public Portal Document
104 East 25th St.. 10th Floor New York, New York 10010 www.atc-enviro.com 212.353.8280 Fax 212.353.8306 ASSOCIATES IWC.
April 19, 2002
Mr. Bernard P. Orlan Director, Environmental Health & Safety New York City Board of Education 28-11 Queens Plaza North Long Island City, NY 11101-4008
Re: Emdoor Air Quality Assessment High School of Economics and Finance (M833) 100 Trinity Place New York, New York 10006 ATC Project No. 15-19125-0291
Dear Mr. Orlan:
ATC Associates Inc. (ATC) is pleased to provide this report of indoor air quality (lAQ) measurements collected on April 18, 2002 at the referenced school. The New York City Board of Education (BOE) requested these measurements as part of a program to determine if acceptable indoor air quality is being maintained.
SCOPE OF WORK
ATC conducted this evaluation to assess the basic parameters of temperature, relative humidity, carbon dioxide (COj) and carbon monoxide (CO).
Total volatile organic compounds (TVOCs) and respirable particulates were also measured.
Kevin Fitzpatrick, Environmental Technician, of ATC’s New York City office, conducted the assessment. ATC’s findings and conclusions are based on a visual inspection, real-time environmental measurements and conditions present in the school at the time of the assessment.
ATC measured temperature, relative humidity, COj and CO with a Q-Trak® Model 8551, manufactured by TSI, Inc.
ATC measured concentrations of respirable particulates (PM2.5) with a Dust-Trak® Aerosol Monitor Model 8520, manufactured by TSI, Inc.
ATC measured concentrations of TVOCs using a RAE Systems, Inc. MiniRAE® photoionization detector (PID).
The assessment was performed consistent with generally accepted indoor air quality assessment practices. As with all such assessments, there were inherent limitations created by constraints of time, operational and work practice variability, variations in indoor air quality parameters and sampling and analytical accuracy.
CITY_21MC100_002879876
NYC-WTC_000383111
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000404508
ATC IAQ field data for High School of Economics and Finance (M833) project 15-19125-0291.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000383107
Indoor air measurements collected April 17, 2002 at the referenced school.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000404504
IAQ measurements at the referenced school; BOE program participation (Apr 17, 2002).
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396645
ATC IAQ measurements collected May 24, 2002 for IAQ assessment.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396715
ATC IAQ measurements collected June 17, 2002 as part of BOE monitoring.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000404489
IAQ measurements conducted at the referenced school as part of BOE program (Apr 16, 2002).
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000383165
ATC notes IAQ measurements performed April 25, 2002 for BOE.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000404538
IAQ report for High School of Economics and Finance (M833) dated Apr 24, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000404522
IAQ measurements collected at the referenced school; BOE program (Apr 22, 2002).
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396711
ATC IAQ measurements collected June 14, 2002 for BOE IAQ program.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000385049
ATC May–June 2002 IAQ report correspondence with BOE about school's air quality.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396719
ATC IAQ measurements collected June 18, 2002 for BOE IAQ maintenance.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000402423
Indoor air quality measurements collected on March 8, 2002 at the referenced school.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000219378
ATC Associates report on indoor air quality measurements collected at the High School of Economics and Finance on April 8, 2002.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402391
IAQ report for High School of Economics and Finance based on measurements collected Mar 4, 2002.
Similarity score 0.995 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000223584
Report of indoor air quality measurements collected at the High School of Economics and Finance on May 15, 2002.
Similarity score 0.994 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000178762
Cover letter from ATC Associates submitting indoor air quality measurements collected at P.S. 150M on May 28, 2002.
Similarity score 0.994 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000383115
IAQ measurements collected April 19, 2002 at the referenced school.
Similarity score 0.994 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Machine-extracted building matches; verify each source. Buildings, never households.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000404508
ATC IAQ field data for High School of Economics and Finance (M833) project 15-19125-0291.
Similar indexed content
NYC-WTC_000383107
Indoor air measurements collected April 17, 2002 at the referenced school.
Similar indexed content
NYC-WTC_000404504
IAQ measurements at the referenced school; BOE program participation (Apr 17, 2002).
Similar indexed content
ATC IAQ measurements collected May 24, 2002 for IAQ assessment.
Similar indexed content
ATC IAQ measurements collected June 17, 2002 as part of BOE monitoring.
Similar indexed content