Mr. Bernard P. Orlan February 8, 2002
Indoor Air Quality Assessment Page 4
P. S. 89M ATC Project No. 15-19125-0297
building was approximately 32 pg/m^ (A.M.) and 52 pg/m^ (P.M.). One (1) A.M. and thirteen
(13) P. M. indoor measurements were above the USEPA recommended concentration of 40
pg/m3 for sensitive individuals such as asthmatic people and children. The outdoor respirable
particulate concentration averaged 54 pg/m^ (A.M.) and 99 pg/m^ (P.M.).
* The measurements made during this assessment were instantaneous readings, the NPAAQS is
a 24-hour average.
TVOC Concentration
TVOCs were not detected (0.0 ppm) anywhere inside or outside the building.
OBSERVATIONS
During this assessment, ATC noted the following;
• The interior of the building appeared clean and free of dust and debris;
• Custodial personnel started buffing the floors after classes finished for the day;
• The school was partially occupied (I.S. 89) at the time of the assessment;
• No smoke odor was detected in the building.
FINDINGS
Based on the real-time measurements, the following findings are presented:
1. Concentrations of CO2, CO and TVOC were within applicable guidelines;
2. Six (6) of the PM2.5 measurements collected in the afternoon were above the NPAAQS of
65 pg/m3. One (1) PM2.5 measurement collected in the morning and thirteen (13) collected
in the afternoon were above the USEPA recommended PM2.5 concentration of 40 pg/nU
for sensitive individuals and children.
3. In the morning, two (2) measurements of temperature were below and six (6) measurements
were above the recommended range. In the afternoon, seven (7) measurements of
temperature were below the recommended range;
4. Fifteen (15) indoor measurements of relative humidity in the afternoon were within the
ASHRAE recommended range of 30 to 60 percent for occupant comfort. All other
measurements were below the recommended range.
It is our pleasure to provide these indoor air quality services to the New York City Board of
Education. If you have any questions about this report, please call (212) 353-8280, extension
261 or212.
Sincerely,
A TC ASSOCL4 TES INC.
Andreas C. Andreou
Senior Project Manager
Attachment
CITY_21MC100_000466571
NYC-WTC_000382578
OCR can misread numbers and units. Confirm readings against the page image before using them.