March 5, 2002
Mr. Bernard P. Orlan Director, Environmental Health & Safety New York City Board of Education 28-11 Queens Plaza North Long Island City, NY 11101 -4008
Re: Indoor Air Quality Assessment P.S. 234M 292 Greenwich Street New York, New York 10007 ATC Project No. 15-19125-0279
Dear Mr. Orlan:
ATC Associates Inc. (ATC) is pleased to provide this report of indoor air quality (TAQi measurements collected on March 4, 2002, at the referenced school. The New York City Board of Education (BOE) requested these measurements as part of a program to detemune if acceptable indoor air quality is being maintained.
SCOPE OF WORK
ATC conducted this evaluation to assess the basic parameters of temperature, relative humidity. carbon dioxide (CO,) and carbon monoxide (CO) with a Q-Trak® Model 8551, manufactured by TSI, Inc.
ATC measured concentrations of respirable particulates (PM2.5) with a Dust-Trak® Aerosol Monitor Model 8520, manufactured by TSI, Inc.
ATC measured concentrations of Total Volatile Organic Compounds (TVOCs) using a RAE Systems, Lie. MiniRAE® photoionization detector (PID).
Mr. Jimmy Choy, Industrial Hygienist of ATC’s New York City office, conducted the assessment.
ATC’s findings are based on a visual inspection, real-time environmental measurements and conditions present in the school at the time of the assessment.
The assessment was performed consistent with generally accepted indoor air quality assessment practices. As with all such assessments, there were inherent limitations created by constraints of time, operational and work practice variability, variations in indoor air quality parameters and sampling and analytical accuracy.
CITY_21MC100_002877619
NYC-WTC_000381333
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000294357
IAQ measurements at P.S. 234M and Greenwich St. school site, dated March 4, 2002.
12 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000314914
Indoor air quality measurements collected at P.S. 234M per BOE program.
12 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000315332
ATC letter accompanying IAQ measurements report for P.S. 234M, June 2002.
12 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000217747
ATC Associates letter reporting indoor air quality measurements collected at P.S. 234M on March 14, 2002, as requested by the NYC Board of Education.
12 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397581
Measurement results from June 3, 2002, evaluating indoor air quality at P.S. 234M per BOE request.
12 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000199221
ATC Associates reports indoor air quality measurements collected at P.S. 234M on June 6, 2002 for the NYC Board of Education.
12 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397611
ATC IAQ measurements collected to determine if acceptable indoor air quality is maintained.
12 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000315321
ATC IAQ measurements at PS 234M; BOE program, June 5, 2002.
12 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000372105
ATC reports IAQ measurements at PS 234M, June 2002, for BOE to assess indoor air quality.
12 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397591
ATC IAQ measurements at PS 234M to determine maintenance of acceptable indoor air quality.
12 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000371885
ATC indoor air quality measurements at PS 234M, April 2002.
12 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000315061
Indoor air quality measurements collected April 26, 2002 for PS 234M.
12 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000294377
Report of IAQ measurements conducted at PS 234M on March 6, 2002.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000308790
Indoor air quality report for PS 234M, measurements Jan–Feb 2002.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000381436
Indoor air quality measurements at PS 234M; March 2002.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000372115
ATC provides IAQ measurements for PS 234M, requested by BOE, June 2002.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000382090
Report of indoor air quality measurements at a New York City school, requested by the Board of Education, Feb 2002.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000371977
ATC IAQ measurements collected May 14, 2002 at PS 234M.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000294357
IAQ measurements at P.S. 234M and Greenwich St. school site, dated March 4, 2002.
Similar indexed content
NYC-WTC_000314914
Indoor air quality measurements collected at P.S. 234M per BOE program.
Similar indexed content
NYC-WTC_000315332
ATC letter accompanying IAQ measurements report for P.S. 234M, June 2002.
Similar indexed content
NYC-WTC_000217747
ATC Associates letter reporting indoor air quality measurements collected at P.S. 234M on March 14, 2002, as requested by the NYC Board of Education.
Similar indexed content
NYC-WTC_000397581
Measurement results from June 3, 2002, evaluating indoor air quality at P.S. 234M per BOE request.
Similar indexed content