NYC 9/11 Public Portal Document
104 East 25ih St,. 10th Floo
New York, New York 1001C
'www.atc-enviro.con
212 353828C
Fax 212 353,830€
ASSOCIATES INC.
May 20, 2002
Mr. Bernard P. Orlan
Director, Environmental Health & Safety
New York City Board of Education
28-11 Queens Plaza North
Long Island City, NY 11101 -4008
Re: Indoor Air Quality Assessment
P.S. 150M
334 Greenwich Street
New York, New York 10013
ATC Project No. 15-19125-0289
Dear Mr. Orlan:
ATC Associates Inc. (ATC) is pleased to provide this report of indoor air quality (lAQ)
measurements collected on May 17, 2002, at the referenced school. The New York City Board
of Education (BOE) requested these measurements to evaluate air quality in the school building
prior to re-occupancy.
SCOPE OF WORK
ATC conducted this evaluation to assess the basic parameters of temperature, relative humidity,
carbon dioxide (CO,) and carbon monoxide (CO).
ATC measured temperature, relative humidity, CO, and CO with a Q-Trak® Model 8551,
manufactured by TSI, Inc.
ATC measured concentrations of respirable particulates (PM2.5) with a Dust-Trak® Aerosol
Monitor Model 8520, manufactured by TSI, Inc.
ATC measured concentrations of Total Volatile Organic Compounds (TVOCs) using a RAE
Systems, Inc. MiniRAE® photoionization detector (PID).
Mr. Jimmy Choy, Environmental Technician, of ATC’s New York City office, conducted the
assessment.
ATC’s findings and conclusions are based on a visual inspection, real-time environmental
measurements and conditions present in the school at the time of the assessment.
CITY_21MC100_002870592
NYC-WTC_000374800
OCR can misread numbers and units. Confirm readings against the page image before using them.