Mr. Bernard P. Orlan June 10. 2002
Indoor Air Quality Measurements Page 3
Stuyvesant High School (M477) ATC Project No. 15-19125-0246
Real-Time Environmental Measurements
ATC collected one hundred and twenty (120) sets of real-time environmental measurements
consisting of one hundred and eighteen (118) in the school building and two (2) outdoors. All
len floors of the school were surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began at 8:00 A.M. and concluded after
12:45 P.M.
Temperature
Indoor dry bulb temperature measurements ranged from 70.2 °F to 74.6 °F. Fifty-two (52) of the
indoor measurements were below the range of 73 to 79°F (at 50 percent relative humidity)
recommended by ASHRAE Standard 55-1992 during the mechanical cooling season
(summertime conditions). The outdoor temperature was 63.8 to 65.1 °F.
Relative Humidity
The relative humidity indoors ranged from 51.7 percent to 62.0 percent. Eleven (11) of the
indoor measurements for relative humidity were above the ASHRAE-recommended range of 30
to 60 percent for occupant comfort. The outdoor relative humidity levels were 53.2 and 54.3
percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 402 ppm to 1144 ppm. Eight (8) of the CO2
measurements were above the ASHRAE Standard 62-1999 recommended maximum
concentration of <700 ppm above the background level. The outdoor (background) CO2
concentrations were 338 ppm and 382 ppm. Therefore, the maximum acceptable level of CO2 at
this location was 1082 ppm (background level -1- 700 ppm). Levels above the recommended
maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator
of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors ranged from 0 ppm to 1 ppm. These concentrations
were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations also
ranged from 0 ppm to 1 ppm.
Respirable Particulates (PM2^5)
Respirable particulate concentrations* indoors ranged between 20 pg/m^ to 31 pg/m^ with an
average of approximately 25 pg/m^. None of the indoor measurements were above the
NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or
less in aerodynamic diameter or above the USEPA recommendation of 40 pg/m^ for sensitive
individuals and children. The outdoor respirable particulate concentrations were 36 and 40
pg/m3.