Indoor air quality report, Stuyvesant High School, May 2002

Machine-extracted title · confidence 40%

May 22, 2002 IAQ measurements at Stuyvesant High School for BOE.

NYC-WTC_000336141–000336145
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan May 23, 2002 Indoor Air Quality Measurements Page 3 Stuyvesant High School (M477) ATC Project No. 15-19125-0246 Real-Time Environmental Measurements

ATC collected one hundred and twenty (120) sets of real-time environmental measurements consisting of one hundred and eighteen (118) in the school building and two (2) outdoors. All ten floors of the school were surveyed. These results are described below.

Field data sheets are found in Attachment 1. Readings began at 8:00 A.M. and concluded after 12:25 P.M.

Temperature

Indoor dry bulb temperature measurements ranged from 68.2°F to 73.5°F. One hundred (100) of the indoor measurements were below (at 50 percent relative humidity) recommended by ASHRAF Standard 55-1992 during the mechanical cooling season (summertime conditions). The outdoor temperature range was 57.3 to 65.4°F.

Relative Humidity

The relative humidity indoors ranged from 30.0 percent to 36.7 percent. All of the measurements were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort.. The outdoor relative humidity levels were 28.5 and 33.2 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 429 ppm to 1176 ppm. Six (6) of the CO2 measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentrations were 391 ppm and 405 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1105 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors ranged from 0 ppm to 1 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations also ranged from 0 ppm to 1 ppm.

Respirable Particulates (PM2,s)

Respirable particulate concentrations* indoors ranged between 8 pg/m^ to 19 pg/m^ with an average of approximately 13 pg/m^. None of the indoor measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommendation of 40 pg/m^ for sensitive individuals and children. The outdoor respirable particulate concentrations were 21 and 22 ugin-.

CITY_21MC1OO_OO3O6O872 NYC-WTC_000336143

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000336143Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000336113

May 2002 IAQ measurements at Stuyvesant High School per BOE request.

Similar indexed content

Compare copies and versions →