104 East 25th St.. 10th Fioor New York, New York 10010 www.atc- etiviro.com 212.3538280 Fax 212.353.8306 ASSOCIATES INC.
June 7, 2002
Mr. Bernard P. Orlan Director, Environmental Health & Safety New York City Board of Education 28-11 Queens Plaza North Long Island City, NY 11101-4008
Re; Indoor Air Quality Assessment Stuyvesant High School (M477) 345 Chambers Street New York, New York 10007 ATC Project No. 15-19125-0246
Dear Mr. Orlan:
ATC Associates Inc. (ATC) is pleased to provide this report of indoor air quality (lAQ) measurements collected on June 6, 2002, at the referenced school. The New York City Board of Education (BOE) requested these measurements as part of a program to determine if acceptable indoor air quality is being maintained.
SCOPE OF WORK
ATC conducted this evaluation to assess the basic parameters of temperature, relative humidity, carbon dioxide (CO,) and carbon monoxide (CO).
Total volatile organic compounds (TVOCs) and respirable particulates were also measured.
Herant Antonyan, Environmental Technician, of ATC’s New York City office, conducted the assessment. ATC’s findings and conclusions are based on a visual inspection, real-time environmental measurements and conditions present in the school at the time of the assessment.
ATC measured temperature, relative humidity, COj and CO with a Q-Trak® Model 8551, manufactured by TSI, Inc.
ATC measured concentrations of respirable particulates (PM2.5) with a Dust-Trak® Aerosol Monitor Model 8520, manufactured by TSI, Inc.
ATC measured concentrations of TVOCs using a RAE Systems, Inc. MiniRAE® photoionization detector (PID).
The assessment was performed consistent with generally accepted indoor air quality assessment practices. As with all such assessments, there were inherent limitations created by constraints of time, operational and work practice variability, variations in indoor air quality parameters and sampling and analytical accuracy.
CITY_21MC100_002868832
NYC-WTC_000373102
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000406906
Indoor air quality measurements at Stuyvesant High School documented for NYC Board of Education, May 2002.
14 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406953
ATC IAQ report for Stuyvesant High School to NYC Board of Education, June 2002.
14 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000213118
Cover letter and report from ATC Associates detailing indoor air quality measurements collected at Stuyvesant High School on June 14, 2002.
14 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000335989
IAQ measurements collected June 20, 2002 at Stuyvesant High School for BOE.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000373107
Indoor air quality measurements collected at Stuyvesant High School in June 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406970
Indoor air quality measurements at Stuyvesant High School prepared for Board of Education, June 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000395300
ATC letter reporting indoor air quality assessment at Stuyvesant High School, June 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000373264
Letter/report detailing indoor air quality measurements at Stuyvesant High School on June 20, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000407007
ATC IAQ report to NYC Board of Education for Stuyvesant High School, June 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000407030
ATC IAQ report for Stuyvesant High School dated June 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000407013
ATC report of IAQ measurements conducted June 20, 2002 at Stuyvesant High School.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000229474
Report from ATC Associates detailing indoor air quality measurements collected at Stuyvesant High School on April 23, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000406753
May 16, 2002 indoor air quality measurements at Stuyvesant High School, for NYC Board of Education.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406576
April 16, 2002 memo documenting IAQ measurements at Stuyvesant High School.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000336204
Indoor air quality measurements collected April 16, 2002 for Stuyvesant High School.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000336182
Indoor air quality measurements at Stuyvesant High School documented April 12, 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406827
May 22, 2002 IAQ report for Stuyvesant High School, Board of Education project 15-19125-0246.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000229474
Report from ATC Associates detailing indoor air quality measurements collected at Stuyvesant High School on April 23, 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000406906
Indoor air quality measurements at Stuyvesant High School documented for NYC Board of Education, May 2002.
Similar indexed content
NYC-WTC_000406953
ATC IAQ report for Stuyvesant High School to NYC Board of Education, June 2002.
Similar indexed content
Cover letter and report from ATC Associates detailing indoor air quality measurements collected at Stuyvesant High School on June 14, 2002.
Similar indexed content
NYC-WTC_000335989
IAQ measurements collected June 20, 2002 at Stuyvesant High School for BOE.
Similar indexed content
Indoor air quality measurements collected at Stuyvesant High School in June 2002.
Similar indexed content