NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan April 23, 2002 Indoor Air Quality Measurements Page 4 Stuvvesant High School fM477) ATC Project No. 15-19125-0246

In addition to higher efficiency rating filters on their HVAC units, portable High Efficiency Particulate Air (HEPA) purifiers were placed in Rooms 327, 333, 638 and 740. The PM2.5 for these rooms concentration ranged from 20 -36 pgZm^ with an average of approximately 28 pg/m3.

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

TVOC Concentration TVOCs inside the building wereO.O ppm for all readings. The outdoor TVOC concentrations were also 0.0 ppm.

OBSERVATIONS

During this assessment, ATC noted die following; • The interior of the building appeared clean and free of dust and debris; • The building was occupied at the time of the assessment; • No smoke odor was detected in the building;

FINDINGS

Based on the real-time measurements, the following findings are presented; 1. Concentrations of CO and TVOCs, were below applicable standards and guidelines. 2. Fifty (50) of the measurements for indoor temperature were below and sixty-eight (68) measurements were within the range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAF Standard 55-1992 during summer conditions. 3. All of the indoor measurements for relative humidity were within the ASHRAE- recommended range of 30 to 60 percent for occupant comfort. 4. Twenty-three (23) measurements were above the ASHRAF Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The highest concentration (1244 ppm) was measured in room 1007 at 12:50 PM with 30 occupants. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration. 5. All of the indoor measurements for PM2.5 were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommendation of 40 pg/m^ for sensitive individuals and children.

CITY_21MC100_002868243

NYC-WTC_000372759

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000372759Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000213095

Cover letter and report from ATC Associates detailing indoor air quality measurements collected at Stuyvesant High School on May 28, 2002.

Similar indexed content

Compare copies and versions →