eOCi WesT Cummings PsrK, Suite 6&00 Woburn, Massachusetts 01801-6350 www.atc-enviro.com 781.932.9400 Fax 781.932.6211 ASSOCIATES INC.

June 28, 2002

Mr. Bernard P. Orlan New York City Board of Education 28-11 Queens Plaza North ' Long Island City, NY 11101

Re: Report of Environmental Sampling Unit Ventilators & HVAC System Stuyvesant High School (M477) ATC Project No. 15-19125-0246

Dear Mr. Orlan:

ATC Associates, Inc. (ATC) conducted environmental sampling at Stuyvesant High School, located at 345 Chambers Street, New York, NY. This testing was conducted on April 27, 2002, at the request of New York City Board of Education (NYCBOE).

The testing included the collection of dust wipe samples for lead analysis and bulk samples for asbestos and dioxin analysis. Representative samples were collected from within the Unit Ventilators and within the HVAC system.

ATC performed a visual inspection within each of the units to be tested to determine if visible dust was present prior to collecting each sample. Samples were collected at locations where visible accumulations of dust were present. Stuyvesant High School Parents Association consultant, Mr. H.A. Bader, was present during the sampling and recommended the locations where the samples were collected.

The analytical results of the testing are as follows:

A. LEAD DUST WIPE SAMPLING -UNIT VENTILATORS

A total of ten (10) dust wipe samples were collected within selected unit ventilators on the north and south sides of the building. Laboratory analysis detected lead concentrations which ranged between 1,902.7 pg/ft^to 500.6 pg/ft^. The average concentration was 1,174.89 pg/ft'- The average concentration on the south side of the building (facing the World Trade Center site) was 1,367.7 pg/fi^, the average on the north side was 982.1 pg/ft^.

CITY_21MC100_002868003

NYC-WTC_000372600

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000372600Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Stuyvesant HS environmental sampling memo

NYC-WTC_000437006

ATC Associates conducted lead dust wipe and asbestos/dioxin bulk sampling at Stuyvesant High School; reports dated Apr 2002.

Similar indexed content

Compare copies and versions →