Indoor air quality report, PS 234M, Jun 2002

Machine-extracted title · confidence 42%

IAQ measurements collected June 26, 2002 at PS 234M.

NYC-WTC_000372233–000372236
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan June 27, 2002 Indoor Air Quality Assessment Page 3 P. S.234M ATC Project No. 15-19125-0279

Real-Time Environmental Measurements

ATC collected sixty (60) sets of real-time environmental measurements consisting of fifty (50) from inside the school building and ten (10) outdoors. All three floors of the school were surveyed. Tliese results are described below.

Field data sheets are found in Attachment 1. Readings began at 07:00 AM and concluded after 12:30 P.M.

Temperature

Indoor dry bulb temperature measurements ranged from 72.1 °F to 75.9 °F. Seven (7) of the indoor measurements for temperature was below the range of 73 to 79°F (at 50 percent relative humidity) as recommended by ASHRAE Standard 55-1992 during the summer season. The outdoor temperature measurements were 76.9 and 78.1 °F.

Relative Humidity

The relative humidity indoors ranged from 50.1 percent to 57.4 percent. All of the indoor measurements for relative humidity were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity measurements were 80.3 and 81.2 percent.

Car^onDioxideConc^ration

Carbon dioxide concentrations indoors ranged from 96 ppm to 1391 ppm. Forty-nine(49) of the indoor measurements were within the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 616 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1316 ppm (background level + 700 ppm). The highest reading (1391 ppm) was recorded in Room 118 approximately at 11:00 AM. with 24 occupants. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 1 ppm for all readings. These concentrations were within the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were also 1 ppm for all readings.

Respirable Particulates (PM2,3)

Respirable particulate concentrations* indoors ranged between 18 pg/m^ to 68 pg/m3 with an average approximately 32 pg/m^- Two (2) of the measurements collected indoors for respirable particulate concentrations were above the NPAAQS 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. Six (6) of the indoor measurements were above the USEPA recommended concentration of 40 pg/m^ for sensitive

CITY_21MC100_002852263

NYC-WTC_000372235

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000372235Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →