Mr. Bernard P. Orlan June 26,2002 Indoor Air Quality Assessment Page 3 P. S. 234M______________ ATC Project No. 15-19125- 0222 ATC collected sixty (60) sets of real-time environmental measurements consisting of fifty (50) from inside the school building and ten (10) outdoors. All three floors of the school were surveyed. These results are described below.
Field data sheets are found in Attachment I. Readings began at 07:00 AM and concluded after 12:51 P.M.
Temperature
Indoor dry bulb temperature measurements ranged from 72.4 °F to 76.3 °F. One (1) of the indoor measurements for temperature was below the range of 73 to 79°F (at 50 percent relative humidity) a.s recommended by ASHRAE Standard 55-1992 during the summer season. The outdoor temperature measurements were 80.1 and 80.4 °F.
Relative Humidity
The relative humidity indoors ranged from 50.1 percent to 59.8 percent. All of the indoor measurements for relative humidity were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity measurements were 56.9 and 57.3 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 561 ppm to 1342 ppm. All of the indoor measurements were within the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) COj concentration was 661 ppm. Therefore, the maximum acceptable level of COj at this location was 1361 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 1 ppm for all readings. These concentrations were within the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were also 1 ppm for all readings.
Respirable Particulates (PM2s)
Respirable particulate concentrations* indoors ranged between 15 pg/m’ to 44 pg/m’ with an average approximately 27 pg/m^' None of the measurements collected indoors for respirable particulate concentrations were above the NPAAQS 65 pg/m’ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. Four (4) of the indoor measurements were above the USEPA recommended concentration of 40 pg/m’ for sensitive individuals and children. The outdoor respirable particulate concentration ranged from 92 pg/m^ to 101 pg/m’ with an average of approximately 98 pg/m’.
* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.
CITY_21MC100_0 02852252
NYC-WTC_000372225
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000315478
ATC IAQ measurements at PS 234M for BOE.
12 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397729
ATC IAQ report for PS 234M; summarizes June 25, 2002 measurements.
12 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000371885
ATC indoor air quality measurements at PS 234M, April 2002.
12 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397365
IAQ measurements collected on Apr 26-29, 2002 for PS 234M.
12 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000315061
Indoor air quality measurements collected April 26, 2002 for PS 234M.
12 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397591
ATC IAQ measurements at PS 234M to determine maintenance of acceptable indoor air quality.
12 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000223930
Cover letter from ATC Associates submitting indoor air quality measurement results for PS 234M collected on May 10, 2002.
12 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397581
Measurement results from June 3, 2002, evaluating indoor air quality at P.S. 234M per BOE request.
12 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397611
ATC IAQ measurements collected to determine if acceptable indoor air quality is maintained.
12 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000199221
ATC Associates reports indoor air quality measurements collected at P.S. 234M on June 6, 2002 for the NYC Board of Education.
12 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000315160
Indoor air quality measurements collected May 10, 2002 at PS 234M.
12 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397665
ATC IAQ measurements to determine if acceptable indoor air quality is being maintained.
12 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000397365
IAQ measurements collected on Apr 26-29, 2002 for PS 234M.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397591
ATC IAQ measurements at PS 234M to determine maintenance of acceptable indoor air quality.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000315321
ATC IAQ measurements at PS 234M; BOE program, June 5, 2002.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397729
ATC IAQ report for PS 234M; summarizes June 25, 2002 measurements.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000315061
Indoor air quality measurements collected April 26, 2002 for PS 234M.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000212729
Cover letter and report from ATC Associates detailing indoor air quality measurements collected at PS 234M on June 5, 2002, for the New York City Board of Education.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000315478
ATC IAQ measurements at PS 234M for BOE.
Similar indexed content
NYC-WTC_000397729
ATC IAQ report for PS 234M; summarizes June 25, 2002 measurements.
Similar indexed content
NYC-WTC_000371885
ATC indoor air quality measurements at PS 234M, April 2002.
Similar indexed content
NYC-WTC_000397365
IAQ measurements collected on Apr 26-29, 2002 for PS 234M.
Similar indexed content
NYC-WTC_000315061
Indoor air quality measurements collected April 26, 2002 for PS 234M.
Similar indexed content