machine-extracted · confidence unavailable · Check page ↗IAQ report for PS 234M dated June 25, 2002, BOE program.
NYC-WTC_000372223–000372226OCR status: ok · source: pdftotext
NYC 9/11 Public Portal Document
600 West Cummings Park, Suite 6500 Woburn. Massachusetts 01801-6350 www.atc-enviro.com 781 932.9400 Fax 781.932.6211 ASSOCIATES INC.
June 26, 2002
Mr. Bernard P. Orlan Director, Environmental Health & Safety New York City Board of Education 28-11 Queens Plaza North Long Island City, NY 11101 -4008
Re: Indoor Air Quality Assessment P.S. 234M 292 Greenwich Street New York, New York 10007 ATC Project No. 15-19125-0279
Dear Mr. Orlan:
ATC Associates Inc. (ATC) is pleased to provide this report of indoor air quality (lAQ) measurements collected on June 25,2002, at the referenced school. The New York City Board of Education (BOE) requested these measurements as part of a program to determine if acceptable indoor air quality is being maintained.
SCOPE OB' WORK
ATC conducted this evaluation to assess the basic parameters of temperature, relative humidity, carbon dioxide (COj) and carbon monoxide (CO) with a Q-Trak® Model 8551, manufactured by TSI, Inc.
ATC measured concentrations of respirable particulates (PMj j) with a Dust-Trak® Aerosol Monitor Model 8520, manufactured by TSI, Inc.
ATC measured concentrations of Total Volatile Organic Compounds (TVOCs) using a RAE Systems, Inc. MiniRAE® photoionization detector (PID).
Mr. Kevin Fitzpatrick, Environmental Technician, of ATC’s New York City office, conducted the assessment.
ATC’s findings are based on a visual inspection, real-time environmental measurements and conditions present in the school at the time of the assessment.
The assessment was performed consistent with generally accepted indoor air quality assessment practices. As with all such assessments, there were inherent limitations created by constraints of time, operational and work practice variability, variations in indoor air quality parameters and sampling and analytical accuracy.
CITY_21MC100_002852250
NYC-WTC_000372223
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000315478
ATC IAQ measurements at PS 234M for BOE.
12 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397729
ATC IAQ report for PS 234M; summarizes June 25, 2002 measurements.
12 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000371885
ATC indoor air quality measurements at PS 234M, April 2002.
12 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397365
IAQ measurements collected on Apr 26-29, 2002 for PS 234M.
12 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000315061
Indoor air quality measurements collected April 26, 2002 for PS 234M.
12 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397591
ATC IAQ measurements at PS 234M to determine maintenance of acceptable indoor air quality.
12 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000223930
Cover letter from ATC Associates submitting indoor air quality measurement results for PS 234M collected on May 10, 2002.
12 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397581
Measurement results from June 3, 2002, evaluating indoor air quality at P.S. 234M per BOE request.
12 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397611
ATC IAQ measurements collected to determine if acceptable indoor air quality is maintained.
12 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000199221
ATC Associates reports indoor air quality measurements collected at P.S. 234M on June 6, 2002 for the NYC Board of Education.
12 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000315160
Indoor air quality measurements collected May 10, 2002 at PS 234M.
12 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397665
ATC IAQ measurements to determine if acceptable indoor air quality is being maintained.
12 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000315478
ATC IAQ measurements at PS 234M for BOE.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000375133
ATC report documents in-situ IAQ measurements at PS 234M, requested by NYC BOE, June 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000182875
Report of indoor air quality measurements collected at PS 234M on February 7, 2002, as part of a program to maintain acceptable air quality.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000272178
Indoor air quality measurements report for PS 234M, Feb 5, 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000315482
ATC IAQ measurements at PS 234M for BOE.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000382038
ATC indoor air quality report for PS 234M, February 2002, BOE request noted.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000315478
ATC IAQ measurements at PS 234M for BOE.
Similar indexed content
NYC-WTC_000397729
ATC IAQ report for PS 234M; summarizes June 25, 2002 measurements.
Similar indexed content
NYC-WTC_000371885
ATC indoor air quality measurements at PS 234M, April 2002.
Similar indexed content
NYC-WTC_000397365
IAQ measurements collected on Apr 26-29, 2002 for PS 234M.
Similar indexed content
NYC-WTC_000315061
Indoor air quality measurements collected April 26, 2002 for PS 234M.
Similar indexed content