Mr. Bernard P. Orlan June 17, 2002 Indoor Air Quality Assessment Page 3 P. S. 234M______________________________ ATC Project No. 15-19125-0279 Real-Time Environmental Measurements
ATC collected sixty (60) sets of real-time environmental measurements consisting of fifty-one (51) from inside the school building and nine (9) outdoors. All three floors of the school were surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began at 7:00 AM and concluded after 12:47 P.M.
Temperature
Indoor dry bulb temperature measurements ranged from 58.6 °F to 74.3 °F. Sixteen (16) of the indoor measurements for temperature were below the range of 73 to 79°F (at 50 percent relative humidity) as recommended by ASHRAE Standard 55-1992 during the summer season. The outdoor temperature measurements were 58.6 °F for all readings.
Relative Humidity
The relative humidity indoors ranged from 53.6 percent to 63.1 percent. One (1) of the indoor measurements for relative humidity was above within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity measurements were 63.1 percent for all readings.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 530 ppm to 1143 ppm. All of the indoor measurements were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) COj concentration was 564 ppm. Therefore, the maximum acceptable level of CO; at this location was 1264 ppm (background level -t 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO; indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 2 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were also 2 ppm for all readings.
Respirable Particulates (PM, i)
Respirable particulate concentrations* indoors ranged between 8 pg/m’ to 22 pg^m" with an average approximately 13 pg/m’ None of the measurements collected indoors for respirable particulate concentrations were above the NPAAQS 65 pg/m’ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter or above the USEPA recommended concentration of 40 pg/m’ for sensitive individuals and children. The outdoor respirable particulate concentration ranged from 21 pg/m’ to 26 pg/m’ with an average of approximately 24 pg/m’.
CITY_21MC100_002852186
NYC-WTC_000372161
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000315193
Indoor air quality measurements collected May 15, 2002 at PS 234M.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000315204
Indoor air quality measurements collected May 16, 2002 at PS 234M.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000372119
ATC IAQ measurements at PS 234M for BOE, June 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397665
ATC IAQ measurements to determine if acceptable indoor air quality is being maintained.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397635
ATC IAQ measurements at PS 234M to evaluate indoor air conditions.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000315372
ATC IAQ measurements report for P.S. 234M prepared for BOE.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397475
ATC IAQ measurements at PS234M, May 15, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397479
ATC reports indoor air quality measurements at PS 234M, May 2002, per BOE request.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000315230
ATC IAQ measurements at PS 234M; BOE program to assess indoor air quality, May 21, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000315270
ATC report of indoor air quality measurements at PS 234M; BOE program, May 29, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397561
ATC IAQ measurements collected May 31, 2002 for PS234M.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000315401
ATC IAQ measurements report for P.S. 234M delivered to BOE.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000397665
ATC IAQ measurements to determine if acceptable indoor air quality is being maintained.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000315204
Indoor air quality measurements collected May 16, 2002 at PS 234M.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397479
ATC reports indoor air quality measurements at PS 234M, May 2002, per BOE request.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397475
ATC IAQ measurements at PS234M, May 15, 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000371997
ATC IAQ measurements at PS 234M, May 16–17, 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000315193
Indoor air quality measurements collected May 15, 2002 at PS 234M.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000315193
Indoor air quality measurements collected May 15, 2002 at PS 234M.
Similar indexed content
NYC-WTC_000315204
Indoor air quality measurements collected May 16, 2002 at PS 234M.
Similar indexed content
NYC-WTC_000372119
ATC IAQ measurements at PS 234M for BOE, June 2002.
Similar indexed content
NYC-WTC_000397665
ATC IAQ measurements to determine if acceptable indoor air quality is being maintained.
Similar indexed content
NYC-WTC_000397635
ATC IAQ measurements at PS 234M to evaluate indoor air conditions.
Similar indexed content