Mr. Bernard P. Orlan May 16, 2002 Indoor Air Quality Assessment Page 3 P. S. 234M________________________ _ ATC Project No. 15-19125-0279 Real-Time Environmental Measurements
ATC collected sixty (60) sets of real-time environmental measurements consisting of fifty-one (51) from inside the school building and nine (9) outdoors. All three floors of the school were surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began at 2;00 P.M. and concluded after 4:30 P.M.
Temperature
Indoor dry bulb temperature measurements ranged from 60 °F to 76 °F. Fifteen (15) indoor measurements for temperature were below the range of 73 to 79°F (at 50 percent relative humidity) as recommended by ASHRAE Standard 55-1992 during the summer season. The outdoor temperature measurements ranged from 56.2 to 61.8 °F.
Relative Humidity
The relative humidity indoors ranged from 25 percent to 36.7 percent. Twenty-five (25) indoor measurements for relative humidity were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 21 to 28.9 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 430 ppm to 870 ppm. All of the measurements were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 391 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1091 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors was 1 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations was 1 ppm for all readings.
Respirable Particulates (PM2j)
Respirable particulate concentrations* indoors ranged between 6 pg/m^ to 26 pg/m^ with an average approximately 12 pg/m^- All measurements collected indoors for respirable particulate concentrations were below the NPAAQS 65 pg/m- 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. The outdoor respirable particulate concentration ranged from 10 pg/m^ to 20 pg/m^ with an average of approximately 16 pg/m^.
CITY_21MC100_002920518
NYC-WTC_000397477
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000315193
Indoor air quality measurements collected May 15, 2002 at PS 234M.
13 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000315204
Indoor air quality measurements collected May 16, 2002 at PS 234M.
13 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397479
ATC reports indoor air quality measurements at PS 234M, May 2002, per BOE request.
13 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397369
Indoor air quality measurements collected on Apr 29, 2002 at PS 234M.
13 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397499
ATC provides IAQ measurements collected May 20, 2002 for PS234M.
13 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000315230
ATC IAQ measurements at PS 234M; BOE program to assess indoor air quality, May 21, 2002.
13 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397665
ATC IAQ measurements to determine if acceptable indoor air quality is being maintained.
13 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397635
ATC IAQ measurements at PS 234M to evaluate indoor air conditions.
13 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000315182
Indoor air quality measurements collected May 14, 2002 for PS 234M.
13 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000315072
ATC IAQ measurements collected April 29, 2002 for P.S. 234M.
13 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397439
ATC IAQ measurements at P.S. 234M per BOE directive, May 2002.
13 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000223944
Cover letter from ATC Associates submitting indoor air quality measurement results for PS 234M collected on May 24, 2002.
13 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000315193
Indoor air quality measurements collected May 15, 2002 at PS 234M.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000315204
Indoor air quality measurements collected May 16, 2002 at PS 234M.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397479
ATC reports indoor air quality measurements at PS 234M, May 2002, per BOE request.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000371997
ATC IAQ measurements at PS 234M, May 16–17, 2002.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397365
IAQ measurements collected on Apr 26-29, 2002 for PS 234M.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397665
ATC IAQ measurements to determine if acceptable indoor air quality is being maintained.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000315193
Indoor air quality measurements collected May 15, 2002 at PS 234M.
Similar indexed content
NYC-WTC_000315204
Indoor air quality measurements collected May 16, 2002 at PS 234M.
Similar indexed content
NYC-WTC_000397479
ATC reports indoor air quality measurements at PS 234M, May 2002, per BOE request.
Similar indexed content
NYC-WTC_000397369
Indoor air quality measurements collected on Apr 29, 2002 at PS 234M.
Similar indexed content
NYC-WTC_000397499
ATC provides IAQ measurements collected May 20, 2002 for PS234M.
Similar indexed content