Mr. Bernard P. Orlan May 15,2092 Indoor Air Quality Assessment Page 3 lf_Y_234M_________________ Al'C Protect No. 15-19125-0279

Rr/Al -Time E^V IRO^^1ENTA1 MliASlIREMENTS

A I C collected si.xty (60i sets of real-time environmental measurements consisting of fifty-one (5 ) from inside the school building and nine (9) outdoors. All three floors ol the school were surveyed. These results are described below.

Field data .'•beets are fourd in Attachment 1. Readings began at 2:00 P.M. and concluded alter 4:30 P.M.

7i’inpernti<re

Indoor dry bulb temperature measurements ranged from 68.3 °F to 77.0°F. Eleven (11) indoor measurement,s for temperature were below the range of 73 to 79°E (at 50 percent relative humidity) recommended by ASIIRAE Standard 55-1992 during the summer season. I'hc outdoor temperature measurements ranged from 53.5 to 60.0 °F.

Relative Hiiiiiiditv

The relative humidity indoors ranged from 27.8 percent to 41.3 percent. Eighteen (IS) indoor measurements for relative humidity were below the ASHRAE-recommended range of .30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 34.6 to 49.8 pci cent.

Carbon dioxide concentrations indoors ranged from 400 ppm to 1016 ppm. All of the measurements were within the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 388 ppm. Therefore, the maximum acceptable level of COp at this location was 1088 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of COp indoors is occupant respiration.

C 'tirhon Monoxide Conceulralion

Carbon mcmoxide concentrations indoors ranged from 0 ppm to 1 ppm. These concentrations were belov the NPAAQS/ASHRAK guideline of 9 ppm. The outdoor CO concentrations were 0 ppm for all readings.

Re^nrahle Particulate tPM? y)

Respirable particulate concentrations* indoors ranged between 12 pg/m^ to 31 pg.'m^ with an average approximately 19 pg/m-< All measurements collected indoors for respirable particulate concentrations were below the NPAAQS 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter or the USEPA recommended concentration of 40 pg/m-^ for sensitive individuals and children. The outdoor respirable particulate concentration ranged from 18 pg/m^ to 27 pg/m-^ with an average of approximately 25 pg/m\

CITY_21MC100_002851944

NYC-WTC_000371979

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000371979Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →