Mr. Bernard P. Orlan May 7,2002 Indoor Air Quality Assessment Page 3 P. S. 234M ATC Project No. 15-19125-0279
Real-Time Environmental Measurements
ATC collected sixty (60) sets of real-time environmental measurements consisting of fifty one (51) from inside the school building and nine (9) outdoors. All three floors of the school were surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began at 2:00 P.M. and concluded after 16:15 P.M.
Temperature
Indoor dry bulb temperature measurements ranged from 68.3 “F to 75.6“F. Ten (10) indoor measurements for temperature were below the range of 73 to 79°F (at 50 percent relative humidity) as recommended by ASHRAE Standard 55-1992 during the summer season. The outdoor temperature measurements ranged from 58.7 to 61.8 °F.
Relative Humidity
The relative humidity indoors ranged from 40.0 percent to 44.2 percent. All indoor measurements for relative humidity were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 56.0 to 57.0 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 609 ppm to 901 ppm. All the measurements were bellow the ASHRyVE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 545 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1245 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 1 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were also 2 ppm for all readings.
Respirable Particulates (PM2,5)
Respirable particulate concentrations* indoors ranged between 19 pg/m^ to 43 pg/m^ with an average 32 pg/m^- All measurements collected indoors for respirable particulate concentrations were below the NPAAQS 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and three (3) measurements were above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. The outdoor respirable particulate concentration ranged from 88 pg/m^ to 96 pg/m^ with an average of 92 pg/m^.
CITY_21MC100_002851889
NYC-WTC_000371931
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000315123
Indoor air quality measurements collected May 6, 2002 for PS 234M.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000315050
Report of IAQ measurements collected April 25, 2002 at PS 234M.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000315134
ATC IAQ measurements at PS 234M for BOE program, May 7, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000315270
ATC report of indoor air quality measurements at PS 234M; BOE program, May 29, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397429
ATC IAQ measurements at PS234M for DOE program, May 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397379
ATC reports IAQ measurements at P.S. 234M, requested by NYC BOE, at 292 Greenwich St, May 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397465
ATC IAQ measurements at PS234M, May 14, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397355
Indoor air quality measurements recorded April 26, 2002 at PS 234M.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397475
ATC IAQ measurements at PS234M, May 15, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000315219
ATC report of IAQ measurements for PS 234M requested by NYC BOE, May 20, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000315193
Indoor air quality measurements collected May 15, 2002 at PS 234M.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397439
ATC IAQ measurements at P.S. 234M per BOE directive, May 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000199213
ATC Associates reports indoor air quality measurements collected at P.S. 234M on May 24, 2002 for the NYC Board of Education.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000315270
ATC report of indoor air quality measurements at PS 234M; BOE program, May 29, 2002.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000199217
ATC Associates reports indoor air quality measurements collected at P.S. 234M on May 30, 2002 for the NYC Board of Education.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000315134
ATC IAQ measurements at PS 234M for BOE program, May 7, 2002.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000315372
ATC IAQ measurements report for P.S. 234M prepared for BOE.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000315171
Indoor air quality measurements collected May 13-14, 2002 at PS 234M.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000315123
Indoor air quality measurements collected May 6, 2002 for PS 234M.
Similar indexed content
NYC-WTC_000315050
Report of IAQ measurements collected April 25, 2002 at PS 234M.
Similar indexed content
NYC-WTC_000315134
ATC IAQ measurements at PS 234M for BOE program, May 7, 2002.
Similar indexed content
NYC-WTC_000315270
ATC report of indoor air quality measurements at PS 234M; BOE program, May 29, 2002.
Similar indexed content
NYC-WTC_000397429
ATC IAQ measurements at PS234M for DOE program, May 2002.
Similar indexed content