Indoor air quality report, 90 Trinity Place

Machine-extracted title · confidence 32%

ATC Associates report of IAQ measurements at High School for Leadership & STEAM, 90 Trinity Place, Mar 1, 2002.

NYC-WTC_000370389–000370392
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan ■March 4, 2002 Indoor Air Quality Assessment Page 4 H.S. for Leadership & Public Service ('M894) ATC Project No. 15-19125-0290

TVOC Concentration

The TVOCs concentrations were 0 ppm inside the building. These concentrations were below the AIHA guideline for odor control of 1 ppm. The outdoor TVOC concentration was also 0 ppm.

OBSERVATIONS

During this assessment, ATC noted the following; • The interior of the building appeared clean and tree of dust and debris; • The building was occupied at the time of the assessment; • No smoke odor was detected in the building;

FINDINGS

Based on the real-time measurements, the following findings are presented:

1. Concentrations of respirable particles, CO and TVOCs were below applicable standards and guidelines. 2. One hundred and seven (107) measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. Twenty-four (24) indoor measurements were within the ASHRAE recommended range. 3. One (1) of the carbon dioxide measurements was above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum acceptable level of CO2 at this location was 1121 ppm (background level -1- 700 ppm). The highest reading (1139 ppm) was found in room 905 at 12:27 PM with 33 occupants. •

It is our pleasure to provide these indoor air quality services to the New York City Board of . Education. If you have any questions about this report, please call (212) 353-8280, extension 336 or 212.

Sincerely, Reviewed by; A TC ASSOCIA TES INC.

■^Amel Ja' h James R. Cohn, CIH, CSP Senior Pi yect Manager Regional Manager Industrial Hygiene Division

Attachment

CITY_21MC100_002865617

NYC-WTC_000370392

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000370392Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000370422

Indoor air quality measurements collected March 6, 2002 at the referenced school.

Similar indexed content

NYC-WTC_000394768

Indoor air quality measurements report for High School for Leadership & [name], Apr 2002.

Similar indexed content

NYC-WTC_000370407

ATC IAQ measurements conducted March 4, 2002 at the referenced NYC BOE school.

Similar indexed content

Compare copies and versions →