Enviroscience TEM AIR SAMPLE RESULTS
Consultants, Inc. CLIENT: American Stock Exchange SAMPLE DATE: December 3,2001
2150 Smithtown Avenue PROJECT NAME: SIAC Computer Room RECEIVED DATE: December 6,2001
Ronkonkoma. New York 1 1779 Ambient
Phone; (631) 5803191 AREA: SAMPLER:
Facsimile: (631) 5803195
L. Savarese
WWW.ENVIROHEALTH.ORG
CLIENT#: 01-10445 CUSTODY #; B-14-02
ELAP# 1 1681
NVLAP #20053 IO
Sample # Sample Location Start End Run Time Flow Rate Volume Filter Cone. Sensitivity Air Cone.
minutes Avg. Liters S/mm2 SZee
TEM AI LI workshop 8:55 9:15 1460 2.14 3066 0.0 0.0016 <Sensitivity
TEMA2 L2 fax/computer rack 9:22 9:18 1436 3.15 4451 0.0 0,0011 <Sensitivitv
TEM A3 L3 desk/console 9:50 9:20 1410 7.35 10293 0.0 0.0005 cSensitivity
TEMA4 L4ACI 10:10 10:20 1460 2.5 3066 0.0 0.0016 <Sensitivity
S=Asbestos structures,cc=cubic centimeters, mm=millimeter
o Analyzed by: '^Date Analyzed: <= less than. Plow Rate in liters per minute
H Samples were analyzed using Philips 400T Transmission Electron Microscope. Asbestos identification is determined by the morphology, visual Selected Area Electron
K Diffraction (SAED), and Elemental Analysis using an Energy Dispersive X-ray Analyzer (EDAX).
I
Concentration on the filter is calculated by taking the number of asbestos structures and dividing by the area analyzed. Air concentration is calculated by multiplying
S
(D
the effective filter area (EFA) by the filter concentration and then dividing by the volume of air collected in cubic centimeters (cc).
The data pertaining to these calculations can be found on the Asbestos Count Sheet.
o
o The air filter concentration relates only to air fiber content. When samples are submitted by an outside agency for analysis, Enviroscience. can only guarantee the
Io accuracy of the filter concentration. TTiis report may not be reproduced without the express permission of Enviroscience. This report can not be used to claim
o endorsement of products by NVLAP or any agency of the U.S. GovemmenL
CO
(JI
The samples collected in the response action area demonstrated a filter concentration of asbestos less than seventy structures per square millimeter. This response
o aebbn is considered complete according to EPA 40 CFR 763.
A result of zero structures per square millimeter is only applicable to the area analyzed. Test results only reflect conditions at the time samples were taken.
CO
NYC-WTC_000367499