NYC 9/11 Public Portal Document
ATC Associates
104 East 25 Street, New York, NY lOOlO
Phone; (212) 353-8280 Fax; (212)353-8306
wc
Attn; Mr. Ben Sallemi Received: 11/17/01 8.00:00 AM
ATC Associates Inc
104 East 25th Street ATC Group#: 5907
New York NY 10010 Analysis Date; 11/19/01
Fax; (212) 353-8306 Phone; (212) 353-8280
Project: 225 Rector Place
225 Rector Place
Asbestos Fiber Analysis by Transmission Electron Microscopy (TEM) Performed
by EPA 40 CFR Part 763 Final Rule (AHERA)
Analytical Asbestos
Hrea Son ^^^bestos Structures Sensitivity Concentration
Sample f/olume .-tnalyzed Asb 0.5fj-5 5u fS/cc) (S/mm^) (S/cc) Notes
I 1300 00 0 0674 0 None Detected 0 0 0 0044 <14 83 <0 0044
5907 -I
7
1300 00 0 0674 Not Analyzed 0 0044 Missing Filter
5907 -2
3 1300 00 0 0674 0 None Detected 0 0 0.0044 <14 83 <0.0044
5907 -3
4 1300 00 0.0674 0 None Detected 0 0 0 0044 <14 83 <0 0044
5907 -4
5 1300 00 0.0674 0 None Detected 0 0 0 0044 <14 83 <0 0044
5907 -5
6 1300,00 0 0674 0 None Detected 0 0 0.0044 <14 83 <0 0044
5907 -6
7 1300 00 0.0674 0 None Detected 0 0 0 0044 <14 83 <0 0044
5907 -7
■ 1300 00 0 0674 0 None Detected 0 0 0 0044 <14 83 <0 0044
5907 -8
MICHAEL GORYCKI MICHAEL A GORYCKl, Ph D
Analyzed by; Aoproved by
Disclaimer The laboratory is not responsible for data reported in structures/cc, which is dependent on volume collected by non-laboratory personnel. This l^s only responsible
for data reported in structures/mm^ This report may not be reproduced, except in full, without wntten approval by ATC Associates Ino, This report may not be used to claim
product endorsement by NVLAP or any other agency of the U S Government This reports relates only to the samples reported above. Quality control data (including 95%
confidence limits and laboratory and analysis' accuracy and precision) is available upon request
Accredited for NVLAP PLM/TEM #101187-0, NY State FLAP #10879