Ambient Group December 13, 2001 memo

Machine-extracted title · confidence 38%

Ambient letter summarizing indoor environmental quality survey.

NYC-WTC_000366064
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

. FAX NO. 212 7B8 1540 P, 02 5-:i THU CP.’55 pr AMBIENT GROUP INC

NAGONAI III MlQUARTWi ambient group inc. $s WFST jgm srKPfcT Indoaf environnwncaL quality surveys I2TTI Ft OCR Water treatment consulting NJ.'W YOAK, NEW' YORK lOOffl Asbestos 6 load field services TL'Ll (112) 944-4615 Regulatory compliance programs TAXI (-12) 94 1-46/8 Air, water ft soil analytical laboratories WDR vww.AMmiiNronouP.co4

December 13, 2001

Mr. Elliot Zuckerman Cushman &^akcfield ;^/a/f Mercantile Exchange One North End Avenue New York, New York 10282

Re: One North End Avenue Ambient Project # 211338

Dear Mr. Zuckerman;

The following is a summary of the indoor environmental quality survey tliat Ambient Group, Inc. performed on December 5, 2001 at One North End Avenue. The survey included sampling for airborne metals (including silica scan), polynuclear aromatic hydrocarbons and airborne asbestos structures by TEM.

Four (4) air samples were collected from floors 3, 7, 10 and 15 and analyzed by transmission electron microscopy (TEM) for asbestos structures. The results of the analysis indicated that airborne asbe.slos levels at the time of testing were less than the analytical sensitivity of the instrument, which is well below the EPA standard of 70 sti'uctures/mm’ as well as other recommended industry guidelines and/or regulations.

four (4) air samples were collected from floors 3, 7, 10 and 15 and analyzed for metals in air {including silica). All measured metals revealed levels well below their respective OSHA PELs and NIOSH RELs. Levels of cristobalite and quartz delected in the silica scan were also below the NIOSH REL of 0.05 mg/m’.

Four (4) air samples were collected from floors 3, 7, 10 and 15 and analyzed for polynuclear aromatic iiydrocarboirs in air. Analysis of ail four (4) samples collected revealed that the levels of the individual compounds were below the OSHA Permissible Exposure Limits and NlOSll REL guidelines.

Please refer to the attached laboratory data sheets for further details. Should you have any queslion.s regarding this information, please feel free to call me.

Sincerely, Signed for Ambient Group, Ino. by;

Vice President

JDnl Attachrnenu CHICAGO, IL CUKONA^CA erxN covr, NY MJAMT, FL ^(6 609-0099 5^7-55 rjog i72-47P 21133R

12/13/01 THU 19:00 ITX/RX NO 8798]

CITY_21MC100_002860918

NYC-WTC_000366064

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000366064Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Ambient Group services proposal, Feb 2002

NYC-WTC_000210392

Fax cover sheet from Ambient Group dated February 12, 2002, offering environmental quality surveys and asbestos field services.

Similar indexed content

Compare copies and versions →