NYC 9/11 Public Portal Document
Aic AbbUClATES, INC
104 E 25th Street, 10th Floor
New York, NY 10010
Teh 212-353-8280
Fax 212-353-8306
REPORT DATE: 08-14-02
CLIENT: Taylor Enviroameiiul Group, Inc.
PROJECT NAME: SCA/Stuyvesant HS
345 Chambers Street, NY
PROJECT NUMBER: M477-15217-29881
SAMPLED BY; CUcnt
SAMPLE DATE: 08-13-02
DATE RECEIVED: 08-13-02
DATE ANALYZED: 08-13-02
SAMPLE MEDIA: Dust Wipe Sample
ANALYSIS REQUIRED: Method EPA 3050/7420
analysis results
SAMPLE BATCH sample description LEAD DETECTION
ID NO. CONCENTRATION LIMIT
(Mg/ft")
LW-01 21112 2nd Floor Corridor Supply 0/S East Stair <9.0 9.0
L'W-02 21112 2nd Floor Corridor Suuply 0/S Rm C221 <9.0 9.0
LW-03 21112 2nd Floor Corridor Supply 0/S West Stair <9.0 9.0
LW-04 21112 2nd Floor Rm 225 Return 14.7 9.0
FB-01 21112 Field Blank <9.0 US 9.0 UE
FB-02 21112 Field Blank <9.0 ug 9-0 pg
NOTE I:
THE REPORTING UMIT (RL) IS 18.0 pg
NOTE 2:
HUD Guidehnes fcir final clearance dust wpe samples Floor 40 Window sills 250 gg/fF,
■ Window wells 400 pg/ft’. Eitcnor surfaces BOO pg/ft’.
NOTES:
Blanic units are in (Jg
ri
ri
CITY_21MC100_002848888
NYC-WTC_000365293
OCR can misread numbers and units. Confirm readings against the page image before using them.