Mr. Bernard P. Orlan February 14,2002
Indoor Air Quality Assessment Page 4
P. S. 89M_ ATC Project No- 15-19125-0297
asthmatic people and children. The outdoor respirable particulate concentration averaged 31
pg/m^ (A-M.) and 11 pg/m^ (P.M.).
* The measurements made during this assessment were instantaneous readings, the NPAAQS is
a 24-hour average.
T7OC Concentration,.
TVOCs were not detected (O.O ppm) anywhere inside or outside the building.
OBSERVATIONS
During this assessment, ATC noted ±e following:
• The interior of die building appeared clean and &ee of dust and debris;
• The school was partially occupied (I.S- 89) at the time of the assessment;
• No smoke odor was detected in the building.
FINDINGS
Based on the real-time measurements, the following findings are presented:
1. Concentrations of PM2.5, CO2, CO and TVOCs were within applicable guidelines.
2. Five (5) temperature measurements were below and two (2) were above the ASHRAE-
recommended range.
3. All indoor measurements of relative humidity were below the ASHRAE recommended range
of 30 to 60 percent for occupant comfort.
It is our pleasure to provide these indoor air quality services to die New York City Board of
Education. If you have any questions about this report, please call (212) 353-82S0, extension
261 or 212.
Sincerely,
ATC ASSOCIATES INC.
Yiannis Efstathiou Jaraes R. Cohn, CIH, CSP
Project Manager Regional Manager
Industrial Hygiene Division