ATC Igl 004/014 02/28/2002 11:38 FAX 212 353 8306

Mr. Bernard P. Orlan February 28,2002 Indoor Air Quality Assessment Page 3 P. S. 89M ATCProiectNo. 15-19125-0297

Real-Time Environmental Measurements

ATC collected eighty (80) sets of real-time environmental measurements consisting of seventy- one (71) ifom inside tire school building and nine (9) from outdoors. All five floors of the school building were surveyed. These results are described below.

Field data sheets are found in Anaclrnent 1. Readings began at 8:00 A.M. and concluded at approximately 11:30 A.M.

Tempeirature

Indoor dry bulb temperature measurements ranged from 68.8°F to 74.6°F. All of the measurements were within the range of 68 to 75°F (at 50 percent relative humidity) as recommended by the ASHRAE Standard 55-1992 dining the heating season (wintertime conditions). The outdoor temperature measurements ranged from 46.0 to 48.3”F.

Relative Humidity

The relative humidity indoors ranged from 23.8 to 33.0 percent. Sixty-seven (67) of the measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The other four (4) measurements were within the ASHRAE-recommcnded range. The outdoor relative humidity measurements ranged from 29.7 to 32.5 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 503 ppm to 1069 ppm. All of the CO2 measurements were within the ASHRAE Srandaro 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 468 ppm. Therefore, the maximum acceptable level of COy at this location was 1168 ppm (background level + 700 ppm). TTie highest CC2 rneasurement was collected from room 526. Levels above tlie recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outside makeup air. The primary source of CO2 indoors is occupant respiration. The school building was occupied during ATC’s assessment.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 0 ppm for all. readings.. These concentrations were below tire NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was also 0 ppm for all collected readings.

Respirable Particulates (PM2,5)

Respirable particulate concentrations* indoors ranged between 9 pg/m^ to 22 None of the measurements were above the NFAAQS of 65 pg/m^ 24-hour average ooncentration of particulate matter 2.5 micrometers or less in aerodynamic diameter, 'Tlie average PM2.5 concentration for the entire school building was approximately 15 The PM2.5 average concentration was below the USEPA recommended concentration of 40 pg/nP for sensitive

CITY_21MC100_012157S19

NYC-WTC_000359777

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000359777Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →