Mr. Bernard P. Orlan January 24, 2002 Indoor Air Quality Assessment Page 3 P, S. 89 (Manhattan) ATC Project No. 15-19125-0297

: i

real-Time Environmental Measurements

ATC collected eighty (80) sets of real-time environmental measurements consisting of seventy- six (76) from inside the school building and four (4) outdoors from the playground. All five floors of the school were surveyed. I’liese results are described below.

Field data sheds are found tn Attachment 1 Readings began at 8:00 A.M. and concluded after 2:30 P.M.

Tsmperett'urs

Indoor dry bulb temperature measurements ranged from 68.0 ®F to 76.0 ®F. Two (2) measurements were above the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature measurements at the playground ranged from 49.1 to 52.0 °F.

Re/ative Humidity

The relative humidity indoors ranged from 18.2 percent to 40.8 percent. Twenty (20) measurements were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. All other measurements were below the recommended range. The outdoor relative humidity ranged from 25.0 to 36.1 percent.

Catbon Dioxidi.' Cimeeniralion

Carbon dioxide concentrations indoors ranged from 480 ppm to 1150 ppin. All CO2 measurements were below the ASH RAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) COo concentrations ranged 458 to 475 ppm. Therefore, the maximum acceptable level of CO2 this location was 1175 ppm (background level -1- 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of COo indoors is occupant respiration. The school building during ATC’s assessment was not occupied.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 0 ppm for all readings. These concentrations were below the NPAAQS/ASIIRAE guideline of 9 ppm. The outdoor CO concentration was 0 ppm.

Re.vpirable Pa]''ticitlate.}i ('PM2_^

Respirable particulate concentrations* indoors ranged between 8 gg/m^ to 17 pg/m^. All measurements were below the NPAAQS of 65 gg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter as well as the USEPA

P0 397d T:TD±V Z2.8028e2TZ TS :60 Z00Z/SZ/T0

CITY_21MC100_012157826

NYC-WTC_000359709

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000359709Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →