AMBIENT AIR AND DUST SAMPLING PROTOCOL for H.S. of Economics and Hnance Page 2 of 8-
• Outside by main entrance - 2 samples (one sample from 8am-12pm & one from 12pm-
4pm)
• Stair case B (open stair case) 7*^ Floor landing - 2 samples (one sample from 8am-12pm
& one from 12pm-4pm)
• Roof - 2 samples (one sample from 8am-12pm & one from 12pm-4pm)
The duration of all ambient air sample shall be approximately 4 hours. The total air volume
sampled at each location shall be approximately 1800 liters.
All ambient air samples collected shall be analyzed via Transmission Electron Microscopy
(TEM) in accordance with the methodology of the AHERA Final Rule.
Results from samples collected each day shall be reported verbally, no later than Sam the
next day, to BOE, UFT, School Principal and the PA consultant. A written report shall be
delivered or faxed by the end of the day. Unsatisfactory results (>7Q s/mm^) shall be reported
immediately.
In the event that any one sample result exceed 70 s/mm^ BOE will immediately notify the
UFT, the school principal, the school custodian and the PA consultant. The said parties will
assess the situation and implement the appropriate response action(s).
INDOOR AIR QUALITY
To address lAQ concerns, each day from Monday through Friday, during school hours, the
following shall be performed:
• A visual inspection to assess conditions present in the school at the time of the site visit.
• Collect approximately 100 real-time environmental measurements of temperature (T)
Collect approximately 100 real-time environmental measurements of relative humidity
(RH)
• Collect approximately 100 real-time environmental measurements of carbon dioxide
(COz)
• Collect approximately 100 real-time environmental measurements of carbon monoxide
(CO)
c
CD
E • Collect approximately 100 real-time environmental measurements of total volatile organic
3
o
o compounds (TVOCs)
Q
TO
o
■c
o
• Collect approximately 100 real-time environmental measurements of respirable 55
Q_ particulates (PM2.5).
o co
o
Z o
3 EVALUATION CRiTERIA: o
0. I
O
05 5
o 6
z z
OCR can misread numbers and units. Confirm readings against the page image before using them.