NYC Law Department release
Independent mirror · updated as the City releases more · v1.5.1
☕ Buy me a coffee
← Document results/Unboxed/No folder label
Document / 4 pages

IAQ memo, school, Sept 9, 2002

Machine-extracted title · confidence 52%

Indoor air quality memo regarding school measurements, Sept 9, 2002.

NYC-WTC_000353570–000353573
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan September 10, 2002 Indoor Air Quality Assessment Page 4 P.S. 42 M ATC Project No. 15-19125-0342 * The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

TVOCConcentrcition

TVOCs concentrations indoors ranged from 0.0 ppm to 0.1 ppm. The AIHA guideline for odor control is 1 ppm. The o atdoor TVOC concentrations were 0.2 ppm and 0.1 ppm.

OBSERVATIONS

During this assessment. ATC noted the following: • The building has no central .MC; • The school was occupied;

FINDINGS

Based on the real-time measurements, the following findings are presented:

1. Concentrations of ('O and TVOCs were within applicable standards and guidelines. 2. Six (6) of the indoor temperature measurements were below the range of 73 to79 °F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the summer season. ASHRAE s tandards do not apply directly to a naturally-ventilated building. 3. Twelve (12) of the indoor measurements for relative humidity were above the ASHRAE- recommended range of 30 to 60 percent for occupant comfort. 4. Forty-five (45) of tlie indoor measurements for PM2.5 were above the USEPA recommended concentration of 4( pg/m^ for sensitive individuals such as asthmatic people and children and above the NPA \QS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. 5. One (1) of indooi measurement for CO2 was above the ASHR.XE Standard 62-2001 recommended maximum concentration of <700 ppm above the background level.

It is our pleasure to provide these indoor air quality services to the New York City Department of Education. If you have my questions about this report, please call (212) 353-8280, extension 211 or 212.

Sincerely, i TC ASSOCIA TES E\ C. Reviewed By:

4 a- A - Yiannis Efstathiou James R. Cohn, CIH, CSP Senior Project Manage! Regional Manager, Industrial Hygiene Division

Attachment

CITY_21MC100_003021527

NYC-WTC_000353573

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000353573Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →