Mr. Bernard P. Orlan September 10, 2002
Indoor Air Quality Assessment Page 4
P.S. 42 M ATC Project No. 15-19125-0342
* The measurements made during this assessment were instantaneous readings, the NPAAQS is
a 24-hour average.
TVOCConcen^tion
TVOCs concentrations indoors ranged from 0.0 ppm to 0.1 ppm. The AIHA guideline for odor
control is 1 ppm. The outdoor TVOC concentrations were 0.2 ppm and 0.1 ppm.
OBSERVATIONS
During this assessment, ATC noted the following:
• The building has no central A/C;
• The school was occupied;
FINDINGS
Based on the real-time measurements, the following findings are presented:
I. Concentrations of CO and TVOCs were within applicable standards and guidelines.
2. Six (6) of the indoor temperature measurements were below the range of 73 to79 °F (at 50
percent relative humidity) recommended by ASHRAE Standard 55-1992 during the summer
season. ASHRAE standards do not apply directly to a naturally-ventilated building.
3. Twelve (12) of the indoor measurements for relative humidity were above the ASHRAE-
recommended range of 30 to 60 percent for occupant comfort.
4. Forty-five (45) of the indoor measurements for PM2.5 were above the USEPA recommended
concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children
and above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5
micrometers or less in aerodynamic diameter.
5. One (1) of indoor measurement for CO2 was above the ASHRAE Standard 62-2001
recommended maximum concentration of <700 ppm above the background level.
It is our pleasure to provide these indoor air quality services to the New York City Department of
Education. If you have any questions about this report, please call (212) 353-8280, extension 211
or 212.
Sincerely,
/I TC ASSOCIA TES INC.
Reviewed By:
James R. Cohn, CIH, CSP
Senior Project Manager Regional Manager, Industrial Hygiene Division
Attachment
CONFIDENTIAL, CITY_21MC100_003422189
SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008
NYC-WTC_000239270
OCR can misread numbers and units. Confirm readings against the page image before using them.