Mr. Bernard P. Orlan September 11, 2002
Indoor Air Quality Assessment Page 4
P.S. 124M ATC Project No. 15-19125-0350
* The measurements made during this assessment were instantaneous readings, the NPAv'iQS is
a 24-hour average.
TVOC Concentration
TVOCs concentrations indoors ranged from 0 ppm to 0.1 ppm. The AIHA guideline for odor
conti’ol IS 1 ppm. The outdoor TVOC concentrations were 0.5 ppm and 0.6 ppm.
OBSERVATIONS
During this assessment, ATC noted the following:
• The building was occupied;
• The building has no central HVAC.
FINDINGS
Based on the real-time measurements, the following findings are presented;
1. Concentrations of CO2, CO and TVOCs were within applicable standards and guidelines.
2. Eighteen (18) of the indoor temperature measurements were above the range of 73 to79 °F
(at 50 percent rela ive humidity) recommended by ASHRAE Standard 55-1992 during the
summer season.
3. All of the indoor measurements for relative humidity were within the ASHRAE-
recommended rang; of 30 to 60 percent for occupant comfort.
4. Fourteen (14) of the indoor measurements for PM2.5 were above the USEPA recommended
concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children.
None of the indoor measurements were above the NPAAQS of 65 pg/m^ 24-hour average
concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter.
It is our pleasure to provide these indoor air quality services to the New York City Department of
Education. If you have any questions about this report, please call (212) 353-8280, extension 211
or 212.
Sincerely,
,(TC ASSOCIA TES INC.
Reviewed By:
-7
-
/Yhannis Efstathio James R. Cohn, CIH, CSP
Senior Project Manager Regional Manager, Industrial Hygiene Division
Attachment
CITY_21MC100_003021052
NYC-WTC_000353301
OCR can misread numbers and units. Confirm readings against the page image before using them.