Airborne asbestos TEM analysis log, NYC DEP

Machine-extracted title · confidence 42%

TEM analysis log for airborne asbestos in NYC DEP project.

NYC-WTC_000347734
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

z ■< z ■<

o o g AIRBORNE ASBESTOS ANALYSIS BY TRANSMISSION ELECTRON MICROSCOPY co O I CLIENT: Warren & Panzer Engineers, P.C. PROJECT: NYC DEP, 55 Warren Street o “0 c o LABORATORY ID T02-11-103 DATE OF REPORT: 11722/02 o CT Ca5 ATHENICA ANALYT. METHODOLOGY: AHERA DATE OF ANALYSIS: 11/22/02 o' ENVIRONMENTAL SERVICES wc FILTER TYPE: M.C.E. EFFECTIVE FILTER AREA (min’): 385 “□ o o Tel. <718) 785-7490 AVERAGE G.O. AREA (mm"): 0 013433 CD Fax. (718) 784-4085 LABORATORY RESULTS C o o c CLIENT # LAB. ID # LOCATION VOLUME G.O.’s AREA ANALYT. TOTAL TOTAL AIR AIR ASBEST. AMPHIB. 3 ANALY SENSITTV. ASBESTOS ASBESTOS CONC. CONC. TYPE ASBEST o (It) ANAL 3 YZED ZED (strucL/cm’) AIR CONC. FILTER FOR FOR CHRYS. TYPE (struc./cm^ CONC. STRUCT. STRUCT. SPECIFY (str./mm’) 0.5<S<5niii S>5.«gm 09 T02-11- Left 1620 4 0.0537 0.0044 <0.0044 <18.61 NA NA NA NA 103-4226 10 T02-11- Middle left 1620 4 0.0537 0.0044 <0.0044 <18.61 NA NA NA NA 103-4227 11 T02-11- Middle 1620 4 0.0537 , 0.0044 <0.0044 <18.61 NA NA NA NA 103-4228 12 T02-11- Middle right 1620 4 0.0537 0.0044 <0.0044 <18.61 NA NA NA NA 103-4229 13 T02-11- Right 1620 4 0.0537 0.0044 <0.0044 <18.61 NA NA NA NA 103-4230

ANALYST LABORATORY DIRECTOR E. Sioukri Spiro Dongaris

LABORATORY CERTIFICATION NUMBERS: NVLAP 101958, ELAP 10955 o • Athenica Environmental Services Inc. (AES), is responsible only for information pertaining to samples taken by its employees. • Air sampling cassettes will be stored for sixty (60) days. AES Inc., should be notified within this time frame for a true duplicate analysis. • If AES Inc., did not conduct the sampling, the reported airborne concentration was derived based on information provided by the client. Under these circumstances, the air concentration data is supplied solely for the convenience of tlie client. S • The report relates only to items tested. This report must not be used to claim product endorsement by NVLAP or any other agency of the U.S. Government. Test reports may not be reproduced o except in full and with prior approval of AES Inc. o • The liability of Athenica Environmental Services Inc. with respect to the services charged, shall in no event exceed the amount of the invoice. 1^ o

co co o

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000347734Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →